Honeywell NOTIFIER NFS-320 Document page 31

Hide thumbs Also See for NOTIFIER NFS-320:
Table of Contents

Advertisement

ESC/MN
trouble
TROUBLE MON
ECS/MN
MNS alarm
5
MONITOR
RF GATEWAY
non-alarm
1 The Drill Switch type code should not be used for Canadian applications.
2 For Canada, the point type is alarm.
3 For proper PAS operation, a CGW-MB may not be installed on the network.
4 LED representation of a CO alarm may be performed using an ACS annunciator.
5 If ECS/MN Override is not selected in VeriFire Tools, fire events will take priority over ECS/MN audio events.
P R O G R A M C O N T R O L
12 spaces for extended
custom label
NOTE: On a control module, the default zone is always set to Zone 00 (general alarm).
Type Code
Silenceable (Y/N) Configuration
CONTROL
Y
RELAY
Y
BELL CIRCUIT
Y
STROBE CKT
Y
HORN CIRCUIT
Y
AUDIBLE CKT
Y
SPEAKER
Y
ISOLATED NAC
Y
ISOLATED SPK
Y
REL END BELL
N
blank
Y
1
REL CKT ULC
N
1
RELEASE CKT
N
1
RELEA.FORM C
N
REL AUDIBLE
Y
NONRESET CTL
N
TELEPHONE
N
1
INSTANT RELE
N
ALARMS PEND.
N
CONTROL NAC
Y
GEN ALARM
N
GEN SUPERVIS
N
GEN TROUBLE
N
GENERAL PEND
N
NFS-320 and NFS-320SYS UL Listing Document — P/N 52745LD:G9 5/19/2022
N
Indicates Trouble on a Mass Notification
device
Y
Does not light any LEDs, overrides existing
fire event, shuts off silenceable outputs and
all fire activated strobes and activates CBE.
Y
Activates CBE
Table 8 Monitor Module Type Codes (2 of 2)
Blinking Type Code selection
M O D U L E C O N T R O L 1 M 1 0 1
0 0 _ _ _ _ _ _ _ _ I O W
Default zone
CBE list
(five zones)
Switch Inhibit: I=selected; *=off (default)
Device Function
NAC
Supervised NAC for notification appliance
Form-C relay
Relay output
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance, used with audio isolators. Activates even if there is
a short on its NAC circuit. For ULC installations only.
NAC
Supervised NAC for speaker circuits, used with audio isolators. Activates even if there is a
short on its audio circuit. For ULC installations only.
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC (for use when no other Type Code applies)
NAC
Releasing Circuit, power-limited (Class 2), supervised for opens, shorts and ground faults
(always non-silenceable)
NAC
Releasing circuit, non-power-limited, supervised for opens and ground faults
Form-C Relay
Relay output, contacts operate upon release
NAC
NAC, activated upon release
Form-C Relay
Relay output, unaffected by "System Reset" command
and NAC
NAC
Standard Telephone circuit
NAC
NAC, short = normal; supervised for open circuits and ground faults. Always non-silenceable
and switch-inhibited.
NAC
Output that will activate upon receipt of an alarm condition, and remain in the alarm state until
all alarms have been acknowledged. It is programmed as "switch inhibit".
NAC
Supervised NAC
NAC
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) configured as a Municipal Box
Transmitter for NFPA 72 Auxiliary Fire Alarm Systems applications. This Type ID can also be
used for general alarm activation. It is programmed as "switch inhibit".
NAC
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any Supervisory
condition (includes sprinkler type). It is programmed as "switch inhibit".
NAC
Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under any System
Trouble condition. It is programmed as "switch inhibit".
NAC
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activate upon receipt of
an alarm and/or trouble condition, and remain in the ON state until all events have been
ACKNOWLEDGED.
Table 9 Control Module Type Codes (1 of 2)
Monitors mass notification devices. Will generate a trouble
condition for both open and short conditions.
Monitors mass notification devices
Provides communication between wireless device and the
fire panel.
20-character user-editable custom label
1 M 1 0 1
SLC address (001-159)
M (module)
SLC number (1 or 2)
Walk Test Selection: *=off
(default); W=selected
Silenceable: O =selected; *=off (default)
31