Honeywell NOTIFIER NFS-320 Document page 28

Hide thumbs Also See for NOTIFIER NFS-320:
Table of Contents

Advertisement

SUP.L(DUCTI)
supervisory
1, 2
SUP.T(ION)
supervisory
2
SUP.L(ION)
supervisory
SMOKE(PHOTO)
fire alarm
SMOKE(DUCTP)
fire alarm
1
SUP.T(DUCTP)
supervisory
SUP.L(DUCTP)
supervisory
1,2
SUP.T(PHOTO)
supervisory
2
SUP.L(PHOTO)
supervisory
RF_PHOTO
fire alarm
3
SMOKE(HARSH)
fire alarm
4
FIRE/CO
fire alarm
2,4,5
FIRE/CO (P SUP)
fire alarm/
supervisory
4
FIRE/CO (C SUP)
fire alarm/
supervisory
Note: For FIRE/CO detectors:
Detectors programmed as FIRE/CO (P SUP), the heat and CO elements will latch and require a system reset to clear. The Photo element will latch or
track, depending on the FIRE/CO (P SUP) setting. Detectors programmed as FIRE/CO (C SUP), the heat and Photo elements will latch and require a
system reset to clear. The CO element will latch or track depending on the FIRE/CO (C SUP) setting.
CO ALARM
CO alarm
CO SUP
CO
supervisory
4
PHOTO/CO
fire
2,4,5
P/CO (P SUP)
photo -
supervisory
CO - Alarm
4
P/CO (C SUP)
Photo - Fire
CO -
supervisory
For PHOTO/CO detectors:
Detectors programmed as PHOTO/CO (P SUP), the heat and CO elements will latch and require a system reset to clear. The Photo element will latch or
track, depending on the PHOTO/CO (P SUP) setting. Detectors programmed as PHOTO/CO (C SUP), the heat and Photo elements will latch and
require a system reset to clear. The CO element will latch or track depending on the PHOTO/CO (C SUP) setting. For Photo/CO and CO Detectors
programmed as Photo/CO (P SUP) or CO (CO SUP) will either latch and track, depending on the setting.
SMOKE(BEAM)
fire alarm
SMOKE(LASER)
fire alarm
28
Y
lights supervisory LED
N
lights supervisory LED
Y
lights supervisory LED
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
N
lights supervisory LED
Y
lights supervisory LED
N
lights supervisory LED
Y
lights supervisory LED
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED for photo and heat, no
LED will light for a CO alarm, photo and heat
will activate CBE, CO alarm activates special
function zone FC and sixth CBE zone only
(sixth CBE zone programmable via VeriFire
Tools)
Y
lights fire alarm LED for heat, no LED will light
for a CO alarm, supervisory LED will light for
photo alarm, heat and photo will activate CBE,
CO alarm activates special function zone FC
and sixth CBE zone only (sixth CBE zone
programmable via VeriFire Tools)
Y
lights fire alarm LED for heat and photo
alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE zone
only (sixth CBE zone programmable via
VeriFire Tools)
Y
CBE Position #5 Activates for CO Pre-alarm,
all other CBEs activate for a CO Alarm
Y (see
CBE Position #5 Activates for CO Pre-alarm,
note on
all other CBEs activate for a CO Supervisory
page 30)
Y
CBE Position #4 activates for CO, CBE
Position #5 Activates for CO Pre-alarm, all
other CBEs activate when the Photo element
activates (i.e. fire alarm)
Y (see
CBE Position #4 activates for CO, CBE
note on
Position #5 Activates for CO Pre-alarm, all
page 30)
other CBEs activate when the Photo element
activates (i.e. Supervisory)
Y
CBE Position #4 activates for CO, CBE
Position #5 Activates for CO Pre-alarm, all
other CBEs activate when the Photo element
activates (i.e. fire alarm)
Y
lights fire alarm LED and activates CBE
Y
lights fire alarm LED and activates CBE
Table 7 Intelligent Detector Type Codes (2 of 3)
NFS-320 and NFS-320SYS UL Listing Document — P/N 52745LD:G9 5/19/2022
Ionization smoke detector used as a duct detector to
report supervisory condition rather than alarm.
Latching.
Ionization smoke detector used to report supervisory
condition rather than alarm. Tracking.
Ionization smoke detector used to report supervisory
condition rather than alarm. Latching.
Photoelectric smoke detector
Duct Photoelectric smoke detector
Photoelectric smoke detector used as a duct detector
to report supervisory condition rather than alarm.
Tracking.
Photoelectric smoke detector used as a duct detector
to report supervisory condition rather than alarm.
Latching.
Photoelectric smoke detector used to report
supervisory condition rather than alarm. Tracking.
Photoelectric smoke detector used to report
supervisory condition rather than alarm. Latching.
Wireless Photoelectric smoke detector
HARSH smoke detector
Photoelectric, Carbon Monoxide, and Heat detector
Photoelectric, Carbon Monoxide, and Heat detector
Photoelectric, Carbon Monoxide, and Heat detector
Carbon Monoxide detector
Carbon Monoxide detector
Photoelectric and Carbon Monoxide detector
Photoelectric and Carbon Monoxide detector
Photoelectric and Carbon Monoxide Detector
Beam smoke detector
Laser smoke detector

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier nfs-320sys

Table of Contents