Canadian Applications - Honeywell NOTIFIER NFS-320 Document

Hide thumbs Also See for NOTIFIER NFS-320:
Table of Contents

Advertisement

NAC Reactivation
Primary power source failure indication
DAC Communication Format
– SIA
– Contact ID
– 4 + 2 Standard
– 4 + 1
– 3 + 1
– 4 + 1 Ademco Express
– 4 + 2 Ademco Express
Interconnected control panels
Alarm, supervisory, and trouble conditions, as well as reset, alarm silence, or trouble silence actuation originating at this panel are annunciated at
this panel. All interconnected panels must also connect to a network annunciator to display these conditions. Acknowledged trouble, supervisory,
alarm and CO events will re-annunciate after 24 hours, if not cleared.
Walk test
Integrated/network local functionality
Circuit disables
Mapping
Detection/alarm algorithms
Day/night sensitivity
Detection sensitivity adjustment
Mass Notification Systems
Extent/limitations of combination system
Priority of signals

Canadian Applications

Standalone Applications:
KDM-R2/C as primary display: An ACS Series annunciator must be mounted adjacent to the fire panel or within the fire panel enclosure
NCA-2/C as primary display: The 640 character, multi-line display complies with ULC requirements when used as a primary display for the fire
panel
Two-Stage Systems (3/5 minute timer) - ACM-24AT control point is required for Automatic Alarm Signal Cancel. Acknowledge will not cancel
the Two-Stage Timer. For applications using Two-Stage with the ACPS-610, see the ACPS-610 manual for additional programming instructions.
Network Applications:
The network's Manual Controls may only be operated from one location at any given time. When panels are networked (using NCM Network
Communications Modules or High-Speed Network Communications Modules), use AKS-1B Key Switch on each panel's Primary Annunciator to
enable its functions. NCA-2/C may be a Primary Annunciator when AKS-1B is installed.
TheNCA-2/C or ONYXWorks may be employed as a Display and Control Center. In the event that communication fails between the panels and
the Control Center, the panels will continue to function in local/standalone mode.
Automatic Alarm Signal Silence:
For a system requiring annunciators, consult the Authority Having Jurisdiction.
Auto Silence:
If auto silence is enabled, the value must be set to 20 minutes
An ACS point is required to monitor special function zone ZF40
Activation of Auto Silence will activate the Signal Silence LED on the fire panel display and any ACM LED point programmed for Auto Silence.
Annunciator Applications:
ACM series annunciator modules must be used to annunciate the fire alarm input points/zones only, if no multi-line sequential display is installed.
The following LED colors must be employed:
– Red must be used to indicate active alarm inputs.
– Yellow must be used to indicate supervisory, burglary, trouble signals, and Automatic Alarm Signal Cancel.
– Green must be used to indicate the presence of power or an activated output.
The ACM point designated for Automatic Alarm Signal Cancel should be labeled as "Automatic Alarm Signal Cancel" or "Auto Alm Signal
Cancel."
If the DCC option is enabled, an ACS control point is required to monitor (request control) ZF36 for the panel, as well as an ACS monitor point
for each DCC on the network. If the DCC option is disabled (subject to AHJ approval), Acknowledge, Signal Silence, and System Reset will
function as stated.
Ancillary Devices
Panel control functions (Acknowledge, Signal Silence, and System Reset will not function on ancillary devices such as the FDU-80 or the LCD2-
80. (Local acknowledge will function on the ancillary device to silence the piezo and steady the LEDs.) If the DCC option is disabled (subject to
AHJ approval), Acknowledge, Signal Silence, and System Reset will function as stated.
Releasing Devices:
Supervision for shorts is required; use REL devices and type code R
(With onboard NACs, use REL-2.2K; with FCM-1 modules use REL-47K.)
NFS-320 and NFS-320SYS UL Listing Document — P/N 52745LD:G9 5/19/2022