Thermostat Circuit Testing - Bradford White D75T125 Troubleshooting Manual And Instructions For Service

Commercial 24 volt flue damper series gas water heater
Hide thumbs Also See for D75T125:
Table of Contents

Advertisement

120 volt exposure. To avoid personal injury,
use caution while performing this procedure.
This procedure assumes the flue damper is in working order. Be sure damper opens under its own power when the
thermostat circuit is by-passed. Damper must be open or removed during this test. Do not force damper open using your
hands or tools.
With power on to water heater,
Verify Primary and secondary voltage at
the transformer
(see photo 3)
THERMOSTAT CIRCUIT BY-PASS
Turn power "OFF" to water heater and
locate thermostat board inside control box
of water heater. Disconnect YELLOW wires
from the thermostat board at location
"N.O." & "COM". Use a jumper to connect
these two wires together
(see photos 4 & 5).
Turn power on to water heater.
Does LED on ignition module illuminate?
(see photo 6)
Y
Does pilot and main burner operate?
Y
Turn power "OFF".
Remove jumper and re-connect wires to
thermostat board. Wires are identified for
proper connection to board.
Disconnect ORANGE potentiometer (temp
adjustment dial) wires from thermostat
board (see photo 7)
Check potentiometer for proper resistance values of:
Greater then 4800 Ohms with dial at minimum setting.
Less than 50 Ohms with dial at maximum setting.
(see photo 8).
Are readings correct?
6
DANGER
Rear terminals
primary
(120 VAC)
Forward terminals
secondary
(24 VAC)
Do not leave thermostat jumper in
place for normal operation.
Verify transformer voltage
N
(see photo 3)
N
See pilot operation testing
6
Be Careful When Making Voltage
Measurements or Jumping Terminals
Not to Damage or Deform Connectors or
3
DANGER
(page 8)
LED Location
N
Replace potentiometer
Check Thermisters
(see page 7)
Y
Page 6
SERVICE PROCEDURE D24-I

Thermostat Circuit Testing

CAUTION
Connector Pins.
4
5
7
8

Advertisement

Table of Contents
loading

Table of Contents