5.2.10 Error 060

Error Conditions and Checklist
Error
E060
Dual venturi error
Check items
Is the dual venturi OFF?
Is the dual venturi closed?
No
Does the dual venturi
repeatedly open
and close?
No
Replace the controller
82
Troubleshooting
Dual venturi wiring is disconnected or the dual venturi malfunctions.
The boiler switches to Lock-out mode, performs a continuous post-purge continuously,
and starts the circulation pump.
1. Check that the dual venturi is operating correctly. Run in dual venturi test mode.
2. Check that the wiring harness is connected correctly and the cables are not damaged.
Yes
Reset the
Yes
Replace the
dual venturi
Dual venturi OFF
Is the dual venturi ON?
Is the dual venturi
boiler
Is the dual venturi wiring
connection correct?
Does the dual venturi
repeatedly open
and close?
Replace the controller
Description
Yes
open?
No
No
Yes
Yes
No
Dual venturi ON
Reset the
boiler
Check the
dual venturi
wiring
Replace the
dual venturi