Error type
Ignition failure
70
Troubleshooting
Cause
When no discharge is seen at the electrode during ignition:
Remove the electrode and check for cracks in the insulator.
Adjust the gap if discharge is visible.
Ensure that the insulating gasket is fitted between the electrode and burner casing.
No spark from the
electrode
Check the input voltage at the ignition transformer (AC 230 V).
If the voltage is correct, replace the ignition transformer.
If there is no or low voltage at the ignition transformer, replace the PCB.
Check the insulator boots on the spark leads for cracks or holes.
Testing method
Ignition gap: 3.5-4.5 mm (1/8")
Ignition transformer