• Large capacity single module units reduce electrical and piping connections. • Dependable operation in extreme ambient conditions down to -13°F in heating and 122°F in cooling. • Refrigerant cooled inverted technology to avoid influence from ambient temperatures. • Corrosion resistant 1000 hr salt spray tested Daikin PE blue fin heat exchanger. • Heat exchanger coil wraps around on all 4 sides of the unit to increase the surface area / efficiency. • Ships factory standard with coil guards. • D igital display on the unit for improved and faster configuration, commissioning, maintenance and troubleshooting of the system.
REYQ-TATJA / TAYDA EDUS371704C-D 2. Compatibility 208/230 V model 460 V model New model New model Current model Current model REYQ72TATJA REYQ72TATJU REYQ72TAYDA REYQ72TAYDU REYQ96TATJA REYQ96TATJU REYQ96TAYDA REYQ96TAYDU REYQ120TATJA REYQ120TAYDA REYQ120TATJU REYQ120TAYDU REYQ144TATJA REYQ144TATJU REYQ144TAYDA REYQ144TAYDU REYQ168TATJA REYQ168TATJU REYQ168TAYDA REYQ168TAYDU REYQ192TATJA REYQ192TAYDA REYQ192TATJU...
REYQ-TATJA / TAYDA EDUS371704C-D 3. Nomenclature Outdoor Unit Minor Revision Power Supply Symbol TJ: 3 phase, 208/230 V, 60 Hz YD: 3 phase, 460 V, 60 Hz Indicates Minor Change Category Indicates Major Design Category Capacity Indication in Cooling Refrigerant Q: R410A Unit category REY: Outdoor unit air cooled heat recovery type...
Page 8
REYQ-TATJA / TAYDA EDUS371704C-D Indoor Unit Standard symbol U: United States of America Power supply symbol VJ: 1 phase, 208/230 V, 60 Hz Indicates major design category Capacity indication in cooling 05: 5,800 Btu/h 18: 18,000 Btu/h 48: 48,000 Btu/h 07: 7,500 Btu/h 24: 24,000 Btu/h 54: 54,000 Btu/h...
Page 9
REYQ-TATJA / TAYDA EDUS371704C-D Branch Selector Unit Single Branch Selector unit (only necessary for Heat Recovery System) Power supply symbol VJ: 1 phase, 208/230 V, 60 Hz Indicates major design category Capacity Indication 36: 36,000 Btu/h 60: 60,000 Btu/h 96: 96,000 Btu/h Refrigerant: R410A Unit category BS: Branch Selector unit...
Page 10
REYQ-TATJA / TAYDA EDUS371704C-D Air Treatment Equipment Outdoor Air Processing Unit Standard symbol U: United States of America Power supply symbol VJ: 1 phase, 208/230 V, 60 Hz Outdoor air processing unit Indicates major design category Capacity indication in cooling 48: 48,000 Btu/h 72: 72,000 Btu/h 96: 96,000 Btu/h...
REYQ-TATJA / TAYDA EDUS371704C-D 4. Model Names Outdoor Units Capacity Range 6 ton 8 ton 10 ton 12 ton 14 ton 16 ton 18 ton 20 ton Power Supply, Standard Capacity Index 208/230 V Heat Recovery REYQ 72TA 96TA 120TA 144TA 168TA 192TA...
REYQ-TATJA / TAYDA EDUS371704C-D Indoor Units Capacity Range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, Standard Capacity Index Ceiling mounted cassette...
REYQ-TATJA / TAYDA EDUS371704C-D Branch Selector Unit Single Branch Selector Unit for Heat Recovery Series Model Name Power Supply, Standard Heat Recovery Note: No interchangeability between BSVQ-PVJU and BSQ-TVJ. VJ: 1 phase, 208/230 V, 60 Hz Multi Branch Selector Unit for Heat Recovery Series Model Name Power Supply, Standard...
REYQ-TATJA / TAYDA EDUS371704C-D Indoor Units Ceiling mounted cassette (Round flow with sensing) type Ceiling mounted duct type FXFQ-T FXMQ-M Shown with BYCQ125B-W1 VISTA™ 2 × 2 cassette unit Ceiling suspended type FXZQ-TA FXHQ-M Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S 4-way blow ceiling-suspended type Wall mounted type FXUQ-P FXAQ-P One way blow cassette type...
REYQ-TATJA / TAYDA EDUS371704C-D Branch Selector Unit Single branch selector unit Multi branch selector unit BSQ-T BS-Q54T Air Treatment Equipment Outdoor air processing unit Energy recovery ventilator (VAM series) FXMQ-MF VAM-G...
REYQ-TATJA / TAYDA EDUS371704C-D 6. Outdoor Unit Combination System capacity Module Number of Outdoor Unit Multi Connection Model name units Piping Kit 1 REYQ72TATJA 21.1 REYQ72TAYDA REYQ96TATJA 10.0 28.1 REYQ96TAYDA REYQ120TATJA 12.5 35.2 — REYQ120TAYDA REYQ144TATJA 15.0 42.2 ...
REYQ-TATJA / TAYDA EDUS371704C-D 7. Interchangeability (Reference) Branch Selector unit New Branch Selector unit Current Branch Selector unit Single Branch Multi Branch Single Branch Multi Branch Selector unit Selector unit Selector unit Selector unit BS4Q54TVJ BSQ36TVJ BS6Q54TVJ BSVQ36PVJU BSV4Q36PVJU BSQ60TVJ BS8Q54TVJ BSVQ60PVJU BSV6Q36PVJU...
*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%. *3. It is permitted to use a maximum connection ratio of 130% in some circumstances – please contact your local Daikin representative for further details.
REYQ-TATJA / TAYDA EDUS371704C-D Capacity Range of Connectable Indoor Units Total capacity index of Maximum number of Type Capacity index Model name connectable indoor units *1 connectable indoor units REYQ72TATJA 36 to 93 (144) REYQ72TAYDA REYQ96TATJA 48 to 124 (192) REYQ96TAYDA Single outdoor REYQ120TATJA...
REYQ-TATJA / TAYDA EDUS371704C-D Limitation of Capacity Index for Heat Recovery Single Branch Selector unit Model BSQ36TVJ BSQ60TVJ BSQ96TVJ Maximum number of connectable indoor units Total capacity index of connectable indoor units unit ≤ 36 36 < unit ≤ 60 60 < unit ≤ 96 Multi Branch Selector unit Model BS4Q54TVJ BS6Q54TVJ BS8Q54TVJ...
REYQ-TATJA / TAYDA EDUS371704C-D 15. Wiring Diagrams REYQ72TATJA NOTES) 1. THIS WIRING DIAGRAM APPLIES ONLY TO THE OUTDOOR UNITS. : FIELD WIRING, : TERMINAL BLOCK, : CONNECTOR, : TERMINAL, : PROTECTIVE GROUND (SCREW), : NOISELESS GROUND. 3. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR. 4.
Page 56
REYQ-TATJA / TAYDA EDUS371704C-D REYQ72TAYDA NOTES) 1. THIS WIRING DIAGRAM APPLIES ONLY TO THE OUTDOOR UNITS. : FIELD WIRING, : TERMINAL BLOCK, : CONNECTOR, : TERMINAL, : PROTECTIVE GROUND (SCREWS), : NOISELESS GROUND. 3. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR. 4.
Low Ambient Cooling mode. It is recommended to locate units away from zones sensitive to sound levels. • Allowable height difference between outdoor and indoor units (when outdoor unit is below) is limited to 130 ft. (40 m). (Normal limit is 195 ft. (60 m).) * Contact your local Daikin representative for wind cover specification requirements and part numbers.
REYQ-TATJA / TAYDA EDUS371704C-D 22. Selection Procedure 22.1 Selection Procedure 22.1.1 Flowchart Given Conditions: · Design temperature and humidity (indoor & outdoor) [1] Given conditions · Required heat load of each room · System peak load (if necessary) · Piping length, level difference ·...
Page 74
REYQ-TATJA / TAYDA EDUS371704C-D 22.1.2 Selection Example The following is a selection example based on total heat load for cooling. Room H Room G Room A Room F Room B Room E Room C Room D Floor plan [1] Given conditions -Design conditions Indoor air temperature: 67°FWB / 75°FDB, Outdoor air temperature: 93°FDB -Determine peak load of each room (and system peak load if necessary)
Page 76
REYQ-TATJA / TAYDA EDUS371704C-D [3] –2 Provisionally select outdoor unit (1) Calculate CI (Capacity Index) of the selected indoor units. CI of VRV indoor units CI of FXMQ15PBVJU = 15 CI of FXMQ18PBVJU = 18 CI of FXMQ36PBVJU = 36 CI of FXMQ48PBVJU = 48 Calculate the total CI of the indoor units.
Page 77
REYQ-TATJA / TAYDA EDUS371704C-D [3] –3 Calculate the corrected capacity of the outdoor unit. -Calculate the combination ratio of the system. Total CI = 234, CI of REYQ192TATJA / TAYDA = 192 Combination ratio = 234 / 192 = 122% - Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for outdoor air temperature, indoor air temperature, and combination ratio.
Page 78
REYQ-TATJA / TAYDA EDUS371704C-D -Confirm capacity correction factor by piping length and level difference (K1) (K1) = 0.924 0.924 -Calculate capacity correction factor by piping heat loss (K2) (K2) = 1 + (heat loss factor per feet of piping × (equivalent piping length – 25 ft.)) / 100 In cooling mode, heat loss factor per feet at 93°F is calculated as below.
REYQ-TATJA / TAYDA EDUS371704C-D 24. Caution for Refrigerant Leaks 24.1 Introduction Points to note in connection with refrigerant leaks The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available. The VRV System, like other air conditioning systems, uses R410A as refrigerant.
REYQ-TATJA / TAYDA EDUS371704C-D 24.2 Procedure for Checking Maximum Concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply. Step1: Calculate the amount of refrigerant (lbs.) charged to each system separately. Amount of refrigerant in a single unit Additional charging amount (amount system (amount of refrigerant with...
Page 95
Step 4: Dealing with the situations where the result exceeds the maximum concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system. Please consult your Daikin supplier.
REYQ-TATJA / TAYDA EDUS371704C-D Appendix 1. Introduction ....................98 1.1 ED Book List ...................98 1.2 Publication List of Engineering Data for VRV Products ....99...
REYQ-TATJA / TAYDA EDUS371704C-D Publication List of Engineering Data for VRV Products Shaded sections indicate Engineering Data Book/s published for this series. Timing of publication is subject to change without notice. Outdoor Unit Refrigerant Category Product series Type Volts Model name Area Book category Book No.
Page 102
REYQ-TATJA / TAYDA EDUS371704C-D Indoor Unit and Other Products Refrigerant Product category Product type Model name Area Book No. Published in Ceiling Mounted Cassette Type FXFQ07-48TVJU EDUS391400A-F14 May 2018 (Round Flow with Sensing) VISTA™ 2 x 2 FXZQ05-18TAVJU EDUS391776-F9 Mar.2018 Cassette Unit 4-Way Blow Ceiling- Suspended FXUQ18-36PVJU...
Page 104
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.