NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
IMPORTANT: This appliance shall only be installed by EPA qualified
personnel having appropriate certification. This appliance is not
intended for use by persons (including children) with reduced physical,
sensory or mental capabilities or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of
the appliance by a person responsible for their safety.
Improper installation, adjustment, alteration, service, maintenance, or
use can cause explosion, fire, electrical shock, or other conditions which
may cause death, personal injury, or property damage. Consult a
qualified installer, service agency, or your distributor or branch for
information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product.
Refer to the individual instructions packaged with the kits or accessories
when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly and follow all
warnings or cautions included in literature and attached to the unit.
Consult local building codes and current editions of the National
Electrical Code (NEC) NFPA 70. In Canada, refer to current editions of
the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety-alert symbol
you see this symbol on the unit and in instructions or manuals, be alert to
the potential for personal injury.
DANGER, WARNING, and CAUTION. These words are used with the
safety-alert symbol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION is
used to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical
disconnect switch must be in the OFF position. There may be more than
1 disconnect switch. Lock out and tag switch with a suitable warning
label.
WARNING
!
EXPLOSION HAZARD
Failure to follow this warning could result in
personal injury or death.
Never use air or any gas containing oxygen for leak
testing or operating refrigerant compressors. Never
allow compressor suction pressure to operate in a
vacuum with service valves closed. See service
manual for pump-down instructions.
Installation Instructions
When
Understand these signal words;
GENERAL
NOTE: In some cases noise in the living area has been traced to gas
pulsations from improper installation of equipment.
1. This unit is intended to be installed in a location that is 10,000 feet
(3000 meters) above sea level or lower.
2. Locate unit away from windows, patios, decks, etc. where unit
operation sound may disturb customer.
3. Ensure that vapor and liquid tube diameters are appropriate for unit
capacity.
4. Run refrigerant tubes with no bends with centerline bend radius less
than 2.5 times the external pipe diameter.
5. Leave some slack between structure and unit to absorb vibration.
6. When passing refrigerant tubes through the wall, seal opening with
RTV or other pliable silicon-based caulk. (See
7. Avoid direct tubing contact with water pipes, duct work, floor
joists, wall studs, floors, and walls.
8. Do not suspend refrigerant tubing from joists and studs with a rigid
wire or strap which comes in direct contact with tubing (see
9. Ensure that tubing insulation is pliable and completely surrounds
vapor tube.
10. When necessary, use hanger straps which are 1 in. (25 mm) wide
and conform to shape of tubing insulation. (See
11. Isolate hanger straps from insulation by using metal sleeves bent to
conform to shape of insulation.
12. Provision shall be made for expansion and contraction of long runs
of piping.
13. Piping and fittings shall be protected as far as possible against
adverse environmental effects. For example, the accumulation of
dirt and debris.
14. Piping should be installed to reduce the likelihood of hydraulic
shock damaging the system.
15. Certified piping and components must be used in order to protect
against corrosion.
16. Flexible pipe elements shall be protected against mechanical
damage, excessive stress by torsion, or other forces. They should be
checked for mechanical damage annually.
17. Piping material, routing, and installation shall be include protection
from physical damage in operation and service, and be in
compliance with the national and local codes and standards of the
installation site.
18. When setting up refrigerant piping, precautions shall be taken to
avoid excessive vibration or pulsation
Fig.
1.)
Fig.
1).
Fig.
1.)

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 34SCA5

  • Page 1 34SCA5 Horizontal Air Conditioner with Puron® Refrigerant 1.5 to 5 Nominal Tons Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS GENERAL IMPORTANT: This appliance shall only be installed by EPA qualified NOTE: In some cases noise in the living area has been traced to gas personnel having appropriate certification.
  • Page 2: Installation

    34SCA5: Installation Instructions transmission of vibration to building. Consult local codes governing OUTDOOR WALL INDOOR WALL rooftop applications. CAULK NOTE: Unit must be level to within ±2° (±3/8 in./ft.±9.5 mm/m) per LIQUID TUBE compressor manufacturer specifications. Rigging SUCTION TUBE INSULATION...
  • Page 3: Fire Hazard

    34SCA5: Installation Instructions Operating Ambient Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 1.) Use refrigerant grade tubing The minimum outdoor operating ambient in cooling mode without Sweat Connection accessory is 55°F (13°C).
  • Page 4 34SCA5: Installation Instructions Install Liquid-Line Filter Drier Indoor Mandatory Requirements IMPORTANT: Installation of filter drier in liquid line is required. Pressure Proof Check Refer to Fig. 3 and install filter drier as follows: 1. Preform a pressure check of the unit with a nitrogen charge of about 200psi.
  • Page 5 34SCA5: Installation Instructions Units with Indoor Piston Air Conditioner Applied as Replacement Component If the air conditioner is installed as a replacement component in an Units installed with indoor pistons require charging by the superheat existing piston indoor system, the piston size in the indoor unit should be method.
  • Page 6 34SCA5: Installation Instructions Table 2 – Rating Plate (required) Subcooling Temperatures R-410A Required Liquid Line Temperature °F (°C) Measure Liquid Pressure °F (°C) °F (°C) °F (°C) °F (°C) °F (°C) °F (°C) (psig) Table 3 – Superheat Charging - AC Only EVAPORATOR ENTERING AIR TEMPERATURE (°F WB)
  • Page 7: Electrical Shock Hazard

    34SCA5: Installation Instructions Connect Ground and Power Wires WARNING This appliance incorporates an earth connection for safety purposes only. Connect ground wire to ground connection in control box for safety. ELECTRICAL SHOCK HAZARD Connect power wiring to contactor as shown in Fig.
  • Page 8: Compressor Crankcase Heater

    34SCA5: Installation Instructions Final Wiring Check Check Charge IMPORTANT: Check factory wiring and field wire connections to Factory charge amount and desired subcooling are shown on unit rating ensure terminations are secured properly. Check wire routing to ensure plate. Charging method is shown on information plate inside unit.
  • Page 9: Final Checks

    34SCA5: Installation Instructions WARNING PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury and/or property damage. For continued performance, reliability, and safety, the only approved accessories and replacement parts are those specified by the equipment manufacturer.
  • Page 10 Access My Learning Center with your HVACpartners credentials at www.mlctraining.com. Please contact us a mylearning@carrier.com with questions. © 2022 Carrier. All rights reserved. Edition Date: 05/22 Catalog No: 34SCA5-01SI Replaces:New Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents