Toshiba G7 Operation Manual page 79

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

F140
F Input Terminal Delay
Program ⇒ Terminal Selection ⇒ Input Terminal Delays ⇒ F
This parameter delays the response of the G7 to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the G7 from responding to contact bounce or chatter.
R Input Terminal Delay
Program ⇒ Terminal Selection ⇒ Input Terminal Delays ⇒ R
This parameter delays the response of the drive to any change in the R terminal
input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the G7 from responding to contact bounce or chatter.
ST Input Terminal Delay
Program ⇒ Terminal Selection ⇒ Input Terminal Delays ⇒ ST
This parameter delays the response of the drive to any change in the ST
terminal input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the G7 from responding to contact bounce or chatter.
RES Input Terminal Delay
Program ⇒ Terminal Selection ⇒ Input Terminal Delays ⇒ RES
This parameter delays the response of the drive to any change in the RES
terminal input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the G7 from responding to contact bounce or chatter.
G7 ASD Operation Manual
Direct Access Number — F140
Parameter Type — Numeric Value
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F141
Parameter Type — Numeric Value
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F142
Parameter Type — Numeric Value
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F143
Parameter Type — Numeric Value
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F143
71

Advertisement

Table of Contents
loading

Table of Contents