Toshiba G7 Operation Manual page 106

Adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

F235
PG Speed Reference Setpoint #1 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference
Setpoints ⇒ PG
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
See
F234
for further information on this setting.
This parameter sets PG Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with the setting of F234.
PG Speed Reference Setpoint #2 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference
Setpoints ⇒ PG
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
See
F234
for further information on this setting.
This parameter sets the PG input pulse count that represents Reference
Setpoint #1 (direction/speed). The range of values for this parameter is -100 to
+100% of the PG input pulse count range.
PG Speed Reference Setpoint #2 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference
Setpoints ⇒ PG
This parameter is used to set the direction, gain, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
See
F234
for further information on this setting.
This parameter sets PG Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F236.
Startup Frequency
Program ⇒ Special Control Parameters ⇒ Frequency Control
The output of the drive will remain at 0.0 Hz until the programmed speed value
exceeds this setting. Once exceeded, the output frequency of the drive will
accelerate to the programmed setting.
Output frequencies below the Startup Frequency will not be output from the
drive during startup.
98
Direct Access Number — F235
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
Direct Access Number — F236
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
Direct Access Number — F237
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
Direct Access Number — F240
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.0
Maximum — 10.0
Units — Hz
G7 ASD Operation Manual
F240

Advertisement

Table of Contents
loading

Table of Contents