Step 5 Purging Inert Gas From The Indoor Unit; Step 6 Cutting And Flaring The Pipes - Samsung AC BNNDCH Series Installation Manual

Table of Contents

Advertisement

Installation Procedure
Step 5 Purging inert gas from the
indoor unit
The indoor unit comes with nitrogen gas (inert gas)
charged at the factory. Therefore, all inert gas must be
purged before connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant
pipe.
Insulator
NOTE
• To prevent dirt or foreign objects from getting into the
pipes during installation, do not remove the pinch pipe
completely until you are ready to connect the piping.

Step 6 Cutting and flaring the pipes

1 Make sure that you have the re uired tools available:
pipe cutter, reamer, flaring tool, and pipe holder.
2 If you wish to shorten the pipes, cut them with a pipe
cutter, ensuring that the cut edge remains at a 90°
angle to the side of the pipe. Refer to the illustrations
below for examples of edges cut correctly and
incorrectly.
Pipe cutter
9 9 0
90°
Pipe
10
English
Li uid side
Gas side
Obli ue
Rough
Burr
3 To prevent any gas from leaking out, remove all burrs
at the cut edge of the pipe, using a reamer.
4 Slide a flare nut on to the pipe and flare the pipe.
D
A
Pipe
Flare
Outer Diameter (D)
Depth (A)
Ø1/4 (6.35)
0.051 (1.3)
Ø3/8 (9.52)
0.071 (1.8)
Ø1/2 (12.70)
0.079 (2.0)
Ø5/8 (15.88)
0.087 (2.2)
5 Check that the flaring is correct, referring to the
illustrations below for examples of incorrect flaring.
Damaged
Correct
Inclined
Surface
R 0.016 to 0.032 inch
(R 0.4 to 0.8 mm)
D
L
Flare dimension (L)
0.34~0.36 (8.7~9.1)
0.50~0.52 (12.8~13.2)
0.64~0.65 (16.2~16.6)
0.76~0.78 (19.3~19.7)
Unit:inch(mm)
Uneven
Cracked
Thickness