Adjustments - Carrier Deluxe 58DLA Installation Manual

Induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in electrical shock,
personal injury, or death.
Blower access door switch opens 115-v power to control. No
component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for
service purposes.
3. To Begin Component Self-Test:
Remove blower access door. Disconnect the thermostat R lead
from the furnace control board. Manually close the blower
door switch closed. Short (jumper) the C
control to the TEST/TWIN 3/16-inch quick connect terminal
on control until LED goes out (approximately 2 sec). Gas
valve and humidifier will not be turned on. (See Fig. 24.)
NOTE: The furnace control allows all components, except the gas
valve, to be run for short period of time. This feature helps
diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is
present at the control.
Component test sequence is as follows:
Refer to service label attached to furnace or see Fig. 55.
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step f of
component test sequence.
c. Hot surface igniter is energized for 15 sec., then off.
d. Blower motor operates on HEAT speed for 10 sec.
e. Blower motor operates on COOL speed for 10 sec.
f. Inducer motor stops.
g. Reconnect R lead to furnace control board, release blower
door switch and re-install blower door.
4. Operate furnace per instruction on door.
5. Verify furnace shut down by lowering thermostat setting
below room temperature.
6. Verify furnace restarts by raising thermostat setting above
room temperature.
Caution!! For the following applications, use the minimum vertical vent heights as specified below.
For all other applications, follow exclusively the National Fuel Gas Code.
FURNACE ORIENTATION
Vent elbow left, then up
Downflow
Horizontal Left
Horizontal Left
Horizontal Left
Vent elbow up then left
Downflow
Vent elbow up, then right
Downflow
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC
*4 in. inside casing or vent guard
**Including 4 in. vent section(s)
-24v terminal on
OM
VENT ORIENTATION
FURNACE INPUT(BTU/HR)
Fig. 38
110,000(036/-12 only)
Vent elbow right,
then up
Fig. 41
Vent Elbow up
Fig. 42
Vent elbow right
Fig. 43
Fig. 36
(036/-12 only)
Fig. 39
(036/-12 only)
Step 3—Adjustments
FIRE HAZARD
Failure to follow this warning could result in reduced furnace
life, property damage, injury, and death.
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result in
excess overfire and heat exchanger failures.
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
DO NOT redrill orifices. Improper drilling (burrs, out-of-
round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of heat exchangers, causing failures. (See Fig.
53.)
Furnace gas input rate on rating plate is for installations at altitudes
up to 2000 ft. Furnace input rate must be within ±2 percent of
furnace rating plate input. For altitudes above 5500 ft., a field-
supplied high altitude pressure switch is required.
1. Determine the correct gas input rate.
In the U.S.A.:
The input rating for altitudes above 2,000 ft. must be reduced
by 4 percent for each 1,000 ft. above sea level. For installa-
tions below 2000 ft., refer to the unit rating plate. For
installations above 2000 ft., multiply the input on the rating
plate by the de-rate multiplier in Table 8 for the correct input
rate.
In Canada:
The input rating must be derated by 10 percent for altitudes of
2,000 ft. to 4,500 ft. above sea level by an authorized Gas
Conversion Station or Dealer. To determine correct input rate
for altitude, see example 1 and use 0.90 as derate multiplier
factor.
2. Determine the correct orifice and manifold pressure adjust-
ment. There are two different orifice and manifold adjustment
tables. All models in all positions, except Low NOx models in
downflow or horizontal positions, use Table 11 (22,000
Btuh/Burner).
Low NOx models in the downflow or horizontal positions
MINIMUM
VENT DIAMETER (IN.)*
154,000
132,000
5
154,000
5
132,000
154,000
5
132,000
154,000
5
110,000
5
110,000
5
34
MINIMUM VERTICAL VENT HEIGHT (FT)**
12
7
7
7
10
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Deluxe 58dlx

Table of Contents