Cleaning Heat Exchanger - Carrier Deluxe 58DLA Installation Manual

Induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

a. Disconnect capacitor wires and ground wire attached to
blower housing.
b. Remove screws securing cutoff plate and remove cutoff
plate from housing.
c. Loosen set screw holding blower wheel on motor shaft
(160+/-20 in.-lb. when reassembling).
d. Remove bolts holding motor to blower housing and slide
motor out of wheel (40+/-10 in.-lb. when reassembling).
e. Remove blower wheel from housing.
f. Clean wheel and housing.
12. Reassemble motor and blower by reversing steps 11f through
11a, finishing with 11a. Be sure to reattach ground wire to the
blower housing.
13. Verify that blower wheel is centered in blower housing and set
screw contacts the flat portion of the motor shaft. Loosen set
screw on blower wheel and reposition if necessary.
14. Spin the blower wheel by hand to verify that the wheel does
not rub on the housing.
15. Reinstall blower assembly in furnace.
16. Reinstall control box assembly in furnace.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shortened heat
exchanger life.
Heating fan speed(s) MUST be adjusted to provide proper air
temperature rise as specified on the rating plate. Recom-
mended operation is at the midpoint of the rise range or
slightly above. Refer to "SET TEMPERATURE RISE" under
START-UP, ADJUSTMENT, and SAFETY CHECK.
NOTE: Refer to Table 9 for motor speed lead relocation if leads
were not identified before disconnection.
17. Reconnect blower leads to furnace control. Refer to furnace
wiring diagram, and connect thermostat leads if previously
disconnected.
18. To check blower for proper rotation:
a. Turn on electrical supply.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in electrical shock,
personal injury, or death.
Blower access door switch opens 115-v power to furnace
control. No component operation can occur unless switch is
closed. Exercise caution to avoid electrical shock from
exposed electrical components when manually closing this
switch for service purposes.
b. Manually close blower access door switch.
NOTE: If thermostat terminals are jumpered at the time blower
access door switch is closed, blower will run for 90 sec before
beginning a heating or cooling cycle.
c. Perform component self-test as shown at the bottom of the
SERVICE label, located on the front of blower access door.
d. Verify blower is rotating in the correct direction
19. If furnace is operating properly, RELEASE BLOWER AC-
CESS DOOR SWITCH. Remove any jumpers or reconnect
any disconnected thermostat leads. Replace blower access
door.
20. Downflow or horizontal furnaces with vent pipe through
furnace only:
a. Install and connect short piece of vent pipe inside furnace
to existing vent.
b. Connect vent connector to vent elbow.
21. Reinstall casing door.
22. Turn on gas supply and cycle furnace through one complete
heating and cooling cycle. Verify the furnace temperature rise
as shown in "Adjustments" Section. Adjust temperature rise as
shown in "Adjustments" Section. If outdoor temperature is
below 70°F, turn off circuit breaker to outdoor unit before
running furnace in the cooling cycle. Turn outdoor circuit
breaker on after completing cooling cycle.

CLEANING HEAT EXCHANGER

The following steps should be performed by a qualified service
agency:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, they should be replaced rather than trying to clean
them thoroughly. A heavy build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as
improper adjustment of manifold pressure, insufficient or poor
quality combustion air, incorrect size or damaged manifold ori-
fice(s), improper gas, or a restricted heat exchanger. Action must
be taken to correct the problem.
If it becomes necessary to clean the heat exchangers because of
dust or corrosion, proceed as follows:
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow or horizontal furnace having an internal vent
pipe, remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark wires to
aid in reconnection of (be careful when disconnecting wires
from switches because damage may occur):
a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switch(es).
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switches.
6. Remove screws that fasten the collector box assembly to the
cell panel. Be careful not to damage the collector box. Inducer
assembly and elbow need not be removed from collector box.
7. Disconnect gas line from gas manifold.
8. Remove the 5 screws that attach the burner assembly to the
cell panel. The gas valve and individual burners need not be
removed from support assembly. Remove NOx baffles if
installed.
NOTE: Be very careful when removing burner assembly to avoid
breaking igniter. See Fig. 57 and 58 for correct igniter location.
9. Using field-provided 25-caliber rifle cleaning brush, 36-in.
long, 1/4" diameter steel spring cable, a variable speed,
reversible electric drill, and vacuum cleaner, clean cells as
follows:
a. Remove metal screw fitting from wire brush to allow
insertion into cable.
45

Advertisement

Table of Contents
loading

This manual is also suitable for:

Deluxe 58dlx

Table of Contents