When shipped from the factory, the SD card will have been pre-installed. It will have been
programmed with the then-current version of the firmware for the GCG001. In the event
the firmware on the SD card needs to be updated, see section 2.7. Note that the firmware
upgrade should be performed before mounting the module.
2.4.2

Mounting the GCG001

The GCG001 is designed to mounted in one of the following ways:
a. In the expansion slot of an RX3i Universal Backplane
b. Panel-mounted
In both cases, at least 75 mm (3 in.) must remain clear above and below the module to allow
for convection cooling. See section 0 for mounting details.
Once the module has been mounted, connect 24Vdc power via the connector on the
underside of the module, connect PROFINET via the RJ-45 connectors and the Genius bus
via twisted pair cable. Each connection is described in the following section.
Once all connections are in place, it will be necessary to configure PROFINET. This is also
discussed in the following sections
Power Connection
The module requires a user-supplied 24Vdc (±10%) power source wired to the removable
screw-terminal block located on the bottom of the module. Connector pin-outs are
identified on the module, as indicated at right. The module draws 0.2 A maximum current.
Figure 9: GCG001 Power Connector
Installation
Chapter 2
Sep 2019
20