Specifications - Emerson PACSystems RX3i User Manual

Genius communications gateway
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User manual
GFK-2892G
1.6

Specifications

RX3i Genius Communications Gateway Specifications
PROFINET Support
CPU Compatibility
PNC001 Compatibility
Embedded PROFINET
Compatibility
PAC* Machine Edition
Compatibility
Power Requirements
Operating Temperature
Range
Number of Port Connectors
Local Area Network (LAN)
Status Data
Genius Bus Support
HHM Compatibility
Other Genius Compatibility
SD Card
Configuration
Hot Swappable
For system standards, general operating specifications, and installation requirements, refer
to the PACSystems RX3i System Manual, GFK-2314.
Introduction
PROFINET version 2.3 Class A IO-Device
RX3i CPE330
RX3i CPE302/CPE305/CPE310 with firmware version 8.15 or
later
RX3i CPU315/CPU320/CRU320 with firmware version 8.15 or
later
Rx3i CPE302 (any firmware version)
Firmware version 2.05 or later
RX3i CPE400 embedded PROFINET
RX3i CPE330 embedded PROFINET with firmware version
8.90 or later
PME 8.0 or later
External 24Vdc: (±10%)
0 to 60°C
Two RJ-45
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100 Mbps
64 (two banks of 32 bits)
Supports One Genius Bus.
Serial 1, Serial 2, Shield in and Shield Out, as marked.
Up to 29 additional devices supported per Genius Bus.
Selectable Baud Rate, per Genius specifications.
Genius Hot Standby and Duplex Redundancy supported.
IC660HHM501
See table in Section 1.11
2GB or smaller. Not compatible with SDHC or SDXC cards.
GSDML file is available on the Support website for download
and import into PME. The GSDML supporting a firmware
release is part of the firmware upgrade kit available on the
Support website.
The Genius Gateway requires an external 24Vdc power supply
and does not draw power from the Rx3i backplane. Swapping
out the GCG001 will therefore not impact the PLC. However,
this cannot be performed without disconnecting its power
supply. If configured to support Genius Hot Standby, the loss
of a single GCG001 will be tolerated; otherwise not.
0.2A
Chapter 1
Sep 2019
6

Advertisement