9 Configuration

a
b
c
c
d
a
Drain hose
b
Caulk this hole with putty or caulking material
c
Adhesive vinyl tape
d
Insulation tape
e
Mounting plate (accessory)
NOTICE
▪ Do NOT bend refrigerant pipes.
▪ Do NOT push the refrigerant pipes onto the bottom
frame or the front grille.
2 Pass the drain hose and refrigerant pipes through the wall hole.
8.3
To fix the unit on the mounting
plate
1 Set the indoor unit on the mounting plate hooks. Use the " "
marks as a guide.
2 Press the bottom frame of the unit with both hands to set it on
the bottom hooks of the mounting plate. Make sure that the
wires do NOT get squeezed anywhere.
Note:
Take care that the interconnection cable does NOT get
caught in the indoor unit.
3 Press the bottom edge of the indoor unit with both hands until it
is firmly caught by the mounting plate hooks.
4 Secure the indoor unit to the mounting plate using 2 indoor unit
fixing screws M4×12L (accessory).
9
Configuration
9.1

To set a different address

In case 2 indoor units are installed in 1 room, different addresses for
2 user interfaces can be set.
1 Remove the batteries from the user interface.
2 Cut the address jumper.
Installation manual
12
e
3 Turn the power supply on.
Result: The flap of the indoor unit will open and close to set the
reference position.
4 Press simultaneously:
Model
FTXF, CTXF, ATXF
5 Press:
Model
FTXF, CTXF, ATXF
6 Select:
Model
FTXF, CTXF, ATXF
7 Press:
Model
FTXF, CTXF, ATXF
8 Press the indoor unit ON/OFF switch while the operation lamp
is blinking.
Jumper
Factory setting
After cutting with nippers
a
a
Address jumper
NOTICE
Be careful NOT to damage any of the surrounding parts
when cutting the address jumper.
INFORMATION
▪ For FTXF, ATXF, CTXF units, the following setting
MUST be completed within 5  minutes after the power
supply is turned on.
▪ In case you could NOT complete the setting in time,
turn the power supply off and wait at least 1  minute
before turning the power supply back on.
Buttons
,
Button
Symbol
Button
ON/OFF
a
Operation lamp
b
Indoor unit ON/OFF switch
Address
1
2
a
and
a
b
CTXF20~35C5V1B
Daikin room air conditioners
3P519299-13V – 2020.08