ABB M4M 30 User Manual page 56

Network analyzer
Hide thumbs Also See for M4M 30:
Table of Contents

Advertisement

56
M4M 30 NETWORK ANALYZER USER MANUAL
PROFIBUS (M4M 30 Profibus product version)
This section is available on M4M 30 Profibus with Profibus DP-V0 embedded communication.
Menu
Address
If DHCP is disabled, the values of above configurations (IP address, subnet mask, gateway, TCP port) are
the default ones. In this case, it is possible to modify each of above configurations.
If DHCP is enabled, it is not needed to enter the above configurations as they are automatically set.
See Profibus communication manual for details on Profibus communication protocol and communication
map.
BACNET (M4M 30 Bacnet product version)
This section is available on M4M 30 Bacnet with BACnet/IP embedded communication.
Parameter
DHCP
IP address
Subnet mask
Gateway
UDP port
Device instance
BBMD
BBMD IP address
BBMD UDP port
BBMD TTL
Ekip Connect mode
Ekip Connect mode item shall be used only for FW upgrade via Ekip Connect desktop. When Ekip Connect
mode is enabled, the device reboots and waits for FW upgrade. At the end of the firmware upgrade
operation the device will reboot with the updated firmware. Once the device has rebooted, ensure that
Ekip connect mode parameter is disabled.
If DHCP is disabled, the values of above configurations are the default ones. In this case, it is possible to
modify each of above configurations.
If DHCP is enabled, it is not needed to enter the above configurations as they are automatically set.
See BACnet communication manual for details on BACnet communication protocol and communication map.
→ Communication → Profibus
Description
From 1 to 126
→ Communication → BACnet
Range
enabled/disabled
0.0.0.0-
255.255.255.255
128.0.0.0-
255.255.255.254
0.0.0.0-
255.255.255.255
0-65535
0-4194302
enabled/disabled
0.0.0.0-
255.255.255.255
0-65535
0-65535
enabled/disabled
Default value
Comments
disabled
This address must create valid
Network prefix and Host address
with combination of subnet mask,
accordingly to IPv4 subnetting.
Additionally some ranges
192.168.1.12
according to IANA organization
are excluded from valid
values: (127.0.0.0-127.0.0.255),
(224.0.0.0-239.255.255.255) and
255.255.255.255.
It must be valid according to IPv4
255.255.255.0
subnetting.
This address follows the same
192.168.1.1
restrictions as IP address of device.
47808
This ID must be unique across
228
BACnet network.
disabled
0.0.0.0
47808
0
disabled

Advertisement

Table of Contents
loading

Table of Contents