Trane UHSB Installation, Operation And Maintenance Manual page 36

S&p unit heaters
Table of Contents

Advertisement

Wiring Installation: S Model
Notice
1.
When using a speed controller,
always locate the thermostat
between the speed controller
and the line, not between the
motor and the controller.
2.
For internal wiring and overload
protection on all starters, consult
the control manufacturer for
details.
3.
When using thermostatic control
with a manual starter, be sure
that the electrical rating of the
thermostat is sufficient to carry
the motor current.
1 PHASE LINE
MANUAL STARTING
SWITCH
MOTOR
MANUAL CONTROL WITH
SINGLE PHASE MOTOR
Figure 47.
1 PHASE LINE
MANUAL STARTING
SWITCH
MOTOR
ROOM THERMOSTAT
THERMOSTATIC CONTROL
WITH MANUAL STARTER
Figure 48.
36
Electrical Connections
1 PHASE LINE
MAGNETIC
STARTING SWITCH
THERMOSTAT
MOTOR
MOTOR
THERMOSTATIC CONTROL
USING MAGNETIC STARTER
OPERATING SEVERAL UNITS
Figure 49.
1 PHASE LINE
MANUAL STARTING
SWITCH
THERMOSTAT
SPEED CONTROLLER
SPEED CONTROLLER WITH
MANUAL STARTING SWITCH
Figure 50.
1 PHASE LINE
MAGNETIC
STARTING SWITCH
THERMOSTAT
MOTORS
SPEED
CONTROLLERS
SPEED CONTROLLERS WITH
MAGNETIC STARTING SWITCH
FOR OPERATING SEVERAL UNITS
Figure 51.
3 PHASE LINE
MOTOR
MANUAL CONTROL WITH
THREE PHASE MOTOR
Figure 52.
3 PHASE LINE
MAGNETIC
STARTING SWITCH
MOTOR
THERMOSTATIC CONTROL
OF SEVERAL THREE PHASE UNITS
Figure 53.
1 PHASE LINE
MANUAL STARTING
SWITCH
MOTOR
ROOM THERMOSTAT
THERMOSTATIC CONTROL WITH
ACTING LIMIT CONTROLLER
AND MANUAL STARTER
Figure 54.
MANUAL STARTING
SWITCH
THERMOSTAT
MOTORS
LIMIT CONTROLLER
REVERSE ACTING
UH-SVX01A-EN