Trane UHSB Installation, Operation And Maintenance Manual page 34

S&p unit heaters
Table of Contents

Advertisement

Wiring Installation: P Model
Notice
1.
When using a speed controller,
always locate the thermostat
between the speed controller
and the line, not between the
motor and the controller.
2.
For internal wiring and overload
protection on all starters, consult
the control manufacturer for
details.
3.
When using thermostatic control
with a manual starter, be sure
that the electrical rating of the
thermostat is sufficient to carry
the motor current.
1 PHASE LINE
MANUAL STARTING
SWITCH
MOTOR
MANUAL CONTROL WITH
SINGLE PHASE MOTOR
Figure 36.
1 PHASE LINE
MANUAL STARTING
SWITCH
MOTOR
ROOM THERMOSTAT
THERMOSTATIC CONTROL
WITH MANUAL STARTER
Figure 37.
34
Electrical Connections
1 PHASE LINE
MAGNETIC
STARTING SWITCH
THERMOSTAT
MOTOR
MOTOR
THERMOSTATIC CONTROL
USING MAGNETIC STARTER
OPERATING SEVERAL UNITS
Figure 38.
1 PHASE LINE
MANUAL STARTING
SWITCH
THERMOSTAT
SPEED CONTROLLER
SPEED CONTROLLER WITH
MANUAL STARTING SWITCH
Figure 39.
1 PHASE LINE
MAGNETIC
STARTING SWITCH
THERMOSTAT
MOTORS
SPEED
CONTROLLERS
SPEED CONTROLLERS WITH
MAGNETIC STARTING SWITCH
FOR OPERATING SEVERAL UNITS
Figure 40.
3 PHASE LINE
MOTOR
MANUAL CONTROL WITH
THREE PHASE MOTOR
Figure 41.
3 PHASE LINE
MAGNETIC
STARTING SWITCH
MOTOR
THERMOSTATIC CONTROL
OF SEVERAL THREE PHASE UNITS
Figure 42.
1 PHASE LINE
MANUAL STARTING
SWITCH
MOTOR
ROOM THERMOSTAT
THERMOSTATIC CONTROL WITH
ACTING LIMIT CONTROLLER
AND MANUAL STARTER
Figure 43.
MANUAL STARTING
SWITCH
THERMOSTAT
MOTORS
LIMIT CONTROLLER
REVERSE ACTING
UH-SVX01A-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uhpb

Table of Contents