Air Filter Requirements; Air Conditioner Installation; Packaging Removal; Rigging And Hoisting - Nordyne P6SD Series User Manual And Installation Instructions

Single package convertible air conditioner
Hide thumbs Also See for P6SD Series:
Table of Contents

Advertisement

• Duct lining must be UL classifi ed batts or blankets with
a fi re hazard classifi cation of FHC-25/50 or less.
• Fiber duct work may be used in place of internal duct
liners if the fi ber duct work is in accordance with the
current revision of the SMACNA construction standard
on fi brous glass ducts. Fibrous duct work and internal
acoustical lining must be NFPA Class 1 air ducts when
tested per UL Standard 181 for Class 1 ducts.

Air Filter Requirements

WARNING:
Never operate the unit without a fi lter in place.
Dust and lint could accumulate on internal parts,
resulting in loss of effi ciency, equipment damage
and possible fi re. Replace disposable fi lters with
the same type and size.
• Air fi lter(s) are not supplied and must be installed in
the unit or in the return air system by the installer. Only
three phase units are equipped with an internal fi lter
rack assembly.
• If using an Economizer or Fresh Air Equipment, the
factory installed fi lter rack must be removed prior to
installation. See page 8 for removal instructions.
• All return air must pass through the fi lters before
entering the unit. Recommended fi lter sizes are listed in
Table 1. NOTE: It is important that all fi lters be kept clean
and replaced frequently to ensure proper operation of
unit. Dirty or clogged fi lters will reduce the effi ciency
of the unit and result in unit shutdowns.
• Air fi lter pressure drop must not exceed 0.08 inches
WC. When replacing the air fi lters, a suitable air fi lter
must be installed upstream of the evaporator coil of
the return air system.
• Downflow Installations require an internal filter
accessory kit to be installed.
• Horizontal Installations require the air fi lter system be
installed in the return air ductwork.
Unit Size
P6SD-X36
P6SD-X48
P6SD-X60
Table 1. Internal Filter Size Requirements.
Internal Filter Size
(2) 16" x 25" x 1"
or
(2) 16" x 25" x 2"
(2) 18" x 25" x 1"
or
(2) 18" x 25" x 2"

AIR CONDITIONER INSTALLATION

Packaging Removal

Remove the shipping carton and User's Manual from
the equipment. Take care not to damage the tubing
connections when removing the carton. For rooftop
installations, remove and discard the two supports
attached beneath the unit.

Rigging and Hoisting

WARNING:
To avoid the risk of property damage, personal
injury, or death, it is the rigger's responsibility
to ensure that whatever means are used to hoist
the unit are safe and adequate:
The lifting equipment must be adequate for the
load. Refer to Table 4 (page 14) for unit weights.
The unit must be lifted from the holes in the
base rails using cables or chains.
Spreader bars are required to protect the unit
and ensure even loading.
Keep the unit in an upright position at all times.
The rigging must be located outside the units
center of gravity. Refer to Figure 9 (page 14)
for locating the center of gravity.
All panels must be securely in place during
rigging and hoisting.

Minimum Clearance Requirements

P6SD units are certifi ed as cooling equipment for
outdoor installation only. Figure 2 (page 6) displays the
minimum clearances to obstructions for both Downfl ow
and Horizontal discharge.
Units may be installed on wood fl ooring or on Class A,
B, or C roof covering material when used with bottom
supply and return air ducts. If using bottom discharge
with return air ducts, a roof curb must be installed prior
to unit installation. See Rigging and Hoisting section for
setting of the unit.

Ground Level

Ground level installations must be located according to
local building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown
in Figure 2.
• A suitable mounting pad (Figure 3, page 8) must be
provided and separate from the building foundation.
The pad must be level to ensure proper condensate
disposal and strong enough to support the unit's weight.
The slab height must be a minimum of 2" (5cm) above
grade and with adequate drainage.
• Allow suffi cient clearances for access to the internal
fi lter rack.
7