6" (15.2cm)
Center Line
2. Install Electrical Service
DANGER: Risk of electrical shock. Connect only to a
properly-grounded, dedicated 120 VAC, 15 A, 60 Hz circuit
protected by a Class A Ground-Fault Circuit-Interrupter (GFCI)
A licensed electrician must install a properly-grounded, dedicated
120 VAC, 15 A, 60 Hz circuit. The circuit must be protected by a
Class A ground-fault circuit-interrupter (GFCI).
Locate the wall box for the flexible conduit to be used for this
circuit 6" (15.2cm) above the floor and 6" (15.2cm) to the right of
the toilet centerline.
Kohler Co.
120 VAC, 15 A,
60 Hz Circuit
6" (15.2cm)
5
1021800-2-B