Care And Maintenance - Carrier 38BYC Installation And Start-Up Instructions Manual

12 seer split system heat pump
Table of Contents

Advertisement

OF2
OF1
O
R
T2
Y
O
R
W2
Y
C
CES0110063,
CES0130024
Fig. 15—Defrost Control
Table 3—Defrost Control Speed-Up
Timing Sequence
MINIMUM
PARAMETER
(MINUTES)
30-minute cycle
27
50-minute cycle
45
90-minute cycle
81
10-minute cycle
5 minutes
4.5
COOLING ONLY PROCEDURE
NOTE: If subcooling charging conditions are not favorable,
charge must be weighed in accordance with unit rating plate ± 0.6
oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
EXAMPLE:
To calculate additional charge required for a 25-ft line set:
25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge
Units installed with cooling mode TXV require charging with the
subcooling method.
1. Operate unit a minimum of 10 minutes before checking
charge.
2. Measure liquid service valve pressure by attaching an accurate
gage to service port.
3. Measure liquid line temperature by attaching an accurate
thermistor type or electronic thermometer to liquid line near
outdoor coil.
4. Refer to unit rating plate for required subcooling temperature.
5. Refer to Table 4. Find the point where required subcooling
temperature intersects measured liquid service valve pressure.
6. To obtain required subcooling temperature at a specific liquid
line pressure, add refrigerant if liquid line temperature is
higher than indicated or reclaim refrigerant if temperature is
lower. Allow a tolerance of ± 3°F.
Copyright 1997 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 101
Catalog No. 563-853
Tab 5a 5a
TI DFT
C
TEST 30 50 90
W1
MAXIMUM
SPEED-UP
(MINUTES)
(NOMINAL)
33
7 sec
55
12 sec
99
21 sec
9
11
2 sec
5.5
1 sec
Printed in U.S.A.
Table 4—Required Liquid-Line Temperature (°F)
LIQUID
PRESSURE AT
SERVICE VALVE
(PSIG)
134
141
148
156
163
171
179
187
196
205
214
223
233
243
253
264
A91444
274
285
297
309
321
331
346
359
HEATING CHECK CHART PROCEDURE
To check system operation during heating cycle, refer to the
Heating Check Chart on outdoor unit. This chart indicates whether
a correct relationship exists between system operating pressure and
air temperature entering indoor and outdoor units. If pressure and
temperature do not match on chart, system refrigerant charge may
not be correct. Do not use chart to adjust refrigerant charge.
NOTE: When charging is necessary during heating season,
charge must be weighed in accordance with unit rating plate ± 0.6
oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
EXAMPLE:
To calculate additional charge required for a 25-ft line set:
25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge
Step 15—Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
1. Securely fasten all panels and covers.
2. Tighten service valve stem caps to 1/12-turn past finger tight.
3. Leave User's Manual with owner. Explain system operation
and periodic maintenance requirements outlined in manual.
4. Fill out Dealer Installation Checklist and place in customer
file.
For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment.
Frequency of maintenance may vary depending upon geographic
areas, such as coastal applications.
Form 38BYC-1SI
REQUIRED SUBCOOLING
TEMPERATURE
(°F)
5
10
71
66
74
69
77
72
80
75
83
78
86
81
89
84
92
87
95
90
98
93
101
96
104
99
107
102
110
105
113
108
116
111
119
114
122
117
125
120
128
123
131
126
134
129
137
132
140
135

CARE AND MAINTENANCE

Pg 12
10-97
Replaces: 38AYC-1SI/38-6SM
15
20
61
56
64
59
67
62
70
65
73
68
76
71
79
74
82
77
85
80
88
83
91
86
94
89
97
92
100
95
103
98
106
101
109
104
112
107
115
110
118
113
121
116
124
119
127
122
130
125
38byc1si

Advertisement

Table of Contents
loading

Table of Contents