Connnection To Am11Magnetic Flow Converter - YOKOGAWA ADMAG AM100D User Manual

Magnetic flow tube
Table of Contents

Advertisement

CAUTION
Since A, B, SA, SB, and C all operate at differ-
ent electrical potentials, securely insulate them
from each other so they do not touch.
The shields must not be allowed to touch each
other or to touch the case.
Cover each shield with vinyl tube or wrap in vinyl
tape.
NOTE
Conductors A and B carry the signal from the
electrodes, and C is at the potentials of the liquid
it self (signal common) . Shields SA and SB are
kept at the same potentials as the individual
electrodes (these are actively driven shields).
This is done to reduce the effect of the distrib-
uted capacitance of the cable at long cable
length. Note that, since the signals from the
individual electrodes are impedance converted
inside the converter, errors will result if they
come in contact with any other component.
Great care must be taken in the cable end
treatment.
(2) Excitation Cable
Please use Polyvinyl chloride insulated and sheathed
control cables (JIS C3401) or Polyvinyl chloride
insulated and sheathed portable power cables (JIS
C3312) or equivalents.
Outer Diameter
• 6.5 to 12mm in diameter (7.5 to 12 mm for water-
proof gland / ECG, /ECU, /ECW)
Nominal Cross Section
• Single wire; 0.5 to 2.5mm
2
2.5mm
85
(3.3)
On the converter side
Figure 3.4.3
End Treatment of Excitation Cable
2
, Stranded wire; 0.5 to
Unit: mm (inch)
85
(3.3)
On the flow tube side
F030403.EPS
3.4.4
Connnection to AM11Magnetic
Flow Converter
Connect the flow tube and converter in the following
method.
EX1
A
B
C
Flow tube
Figure 3.4.4
Connection
3-17
3. INSTALLATION
C SA A
B
SB
AM11
converter
EX2
Dedicated signal cable
AM011-2
Converter
Flow tube
Terminal
SA
(See Note below)
A
EX2
B
(See Note below)
SB
C
EX1
EX2
EX1
Note: Terminate those shielding wire terminal
using insulating tape.
A
B
C
EX1
EX2
F030404.EPS
IM 1E6D0-01E