Table 10 — HH57AC081 Sensor Wiring Terminations
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
Use Fig. 47 and Table 11 to set the DIP switches for the desired
use of the sensor.
Table 11 — HH57AC081 Sensor DIP Switch
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
NOTE: When an S-Bus sensor is connected to an existing net-
work, it will take 60 minutes for the network to recognize and
auto-configure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor fail-
ures (except SAT) will be issued and no economizing function
will be available.
CO
SENSOR WIRING
2
When using a CO
sensor the black and brown common wires
2
are internally connected and only one is connected to "IAQ
COM" on the W7220 (see Fig. 46). Use the power from the
W7220 to power the CO
sensor OR make sure the ground for
2
the power supplies are common. See Fig. 48 for CO
wiring.
CO
SENSOR
2
24V
+
ANALOG
OUT
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Fig. 48 — CO

INTERFACE OVERVIEW

This section describes how to use the EconoMi$er
terface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a 4-but-
ton keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 49) to scroll through
the menus and menu items, select menu items, and to change
parameter and configuration settings.
To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous
menu.
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
2
3
ON
OFF
OFF
OFF
OFF
OFF
2
RED
L1
(HOT)
BLACK
L2
1
YELLOW
BROWN
ORANGE
GREEN
Sensor Wiring
2
X user in-
®
Press the ▼ (Down arrow) button to move to the next
menu.
Press the
currently displayed menu.
Press the
and return to the list of menus.
MENU UP
(EXIT)
BUTTON
Fig. 49 — W7220 Controller Navigation Buttons
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2. Press the
currently displayed menu.
3.
Use the ▲ and ▼ buttons to scroll to the desired parameter.
sensor
4. Press the
currently displayed item.
5. Press the ▲ button to increase (change) the displayed
parameter value.
6. Press the ▼ button to decrease (change) the displayed
parameter value.
NOTE: When values are displayed, pressing and holding the ▲or
▼ button causes the display to automatically increment or
decrement.
1. Press the
and store it in nonvolatile RAM. "CHANGE STORED"
displays.
2. Press the
parameter.
3. Press the
ous menu.
Menu Structure
Table 12 illustrates the complete hierarchy of menus and pa-
rameters for the EconoMi$er
The Menus in display order are:
STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
CHECKOUT
ALARMS
29
(Enter) button to display the first item in the
(Menu Up/Exit) button to exit a menu's item
SCROLL
UP/DOWN
BUTTONS
(Enter) button to display the first item in the
(Enter) button to display the value of the
(Enter) button to accept the displayed value
(Enter) button to return to the current menu
(Menu Up/Exit) button to return to the previ-
X system.
®
2 LINE
LCD
SELECT
(ENTER)