APPENDIX A
AIR CONDITIONER AND HEAT PUMP
WITH PURON
QUICK REFERENCE
GUIDE
S Puron (R-410A) refrigerant operates at 50 percent to
70 percent higher pressures than R-22. Be sure that
servicing equipment and replacement components are
designed to operate with Puron.
S Puron refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400
psig, DOT 4BA400 or DOT BW400.
S Puron systems should be charged with liquid
refrigerant. Use a commercial type metering device in
the manifold hose when charging into suction line with
compressor operating.
S Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low-side retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC
refrigerant.
S Puron, as with other HFCs, is only compatible with
POE oils.
S Vacuum pumps will not remove moisture from oil.
S Use only factory specified liquid-line filter driers with
rated working pressures greater than 600 psig.
APPENDIX B
WIRING DIAGRAM LIST
Cooling
Unit
Electrical Characteristics
Stages
575J*07A/B
1
575J*07G/H
2
575J*08A/B
1
575J*12A/B
1
575J*12G/H
2
S Do not install a suction-line filter drier in liquid-line.
S POE oils absorb moisture rapidly. Do not expose oil to
atmosphere.
S POE oils may cause damage to certain plastics and
roofing materials.
S Wrap all filter driers and service valves with wet cloth
when brazing.
S A factory approved, liquid-line filter drier is required on
every unit.
S Do not use an R-22 TXV.
S If indoor unit is equipped with a TXV, it must be
changed to a Puron TXV.
S Never open system to atmosphere while it is under a
vacuum.
S When system must be opened for service, recover
refrigerant, break vacuum with dry nitrogen before
opening system.
S Always replace filter drier after opening system for
service.
S Do not vent Puron into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.
S All Puron heat pumps must have indoor TXV.
S Do not leave Puron suction line driers in place for
more than 72 hours.
Diagram Number
208/230-3-60
38AU500363
460-3-60
38AU500362
575-3-60
38AU500435
208/230-3-60
38AU000443
460-3-60
38AU000443
575-3-60
38AU000444
208/230-3-60
38AU500363
460-3-60
38AU500362
575-3-60
38AU500435
208/230-3-60
38AU500363
460-3-60
38AU500362
575-3-60
38AU500435
208/230-3-60
38AU000445
460-3-60
38AU000445
575-3-60
38AU000446
46

Advertisement

Table of Contents
loading

Table of Contents