Electromagnetic compatibility
Interference immunity to
electrostatic discharge
radiated, radio-frequency, electromagnetic field
electrical fast transient/burst
surge
conducted disturbances, induced by radio-
frequency fields
voltage dips, short interruptions and voltage
variations
Interference emission
high-frequency radiated
high-frequency conducted
limits for harmonic current emissions
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
IEC/EN 61000-6-2
IEC/EN 61000-4-2
Level 4 (8 kV / 15 kV)
IEC/EN 61000-4-3
Level 3 (10 V/m)
IEC/EN 61000-4-4
input circuit: Level 4 (4 kV)
output circuit: Level 3 (2 kV)
IEC/EN 61000-4-5
input circuit: L-L Level 3 (2 kV) / L-PE Level 4 (4 kV)
output circuit: Level 1 (0.5 kV)
IEC/EN 61000-4-6
Level 3 (10 V, 150 kHz - 80 MHz)
IEC/EN 61000-4-11
Class 3
IEC/EN 61000-6-3
IEC/CISPR 22, EN 55022
Class B
IEC/CISPR 22, EN 55022
Class B
IEC/EN 61000-3-2
Class A