Daikin J Series Service Manual page 224

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

Outdoor Unit - RK(X)S42J2V1B
Step
4
Remove the protection
bushing.
5
Remove the 2 nuts of
the compressor.
Before working, make
sure that the refrigerant
gas is empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
6
Heat up the brazed part
of the discharge side
and disconnect.
Heat up the brazed part
7
of the suction side and
disconnect.
213
Procedure
Protection bushing
Points
(R8199)
Warning
(R0265)
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Warning
Since it may happen that the
refrigerant oil in the
compressor catches fire,
prepare wet cloth so as to
(R8201)
extinguish fire immediately.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
Removal Procedure
SiBE041101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents