Toshiba RAV-HM301MUT-E Service Manual page 29

Hide thumbs Also See for RAV-HM301MUT-E:
Table of Contents

Advertisement

No.
Item
6
Fan speed
selection
Outline of specifications
1) Operation with (HH), (H+), (H), (L+) (L) or [AUTO] mode
is carried out by the command from the remote controller.
2) When the fan speed mode [AUTO] is selected, the fan
speed varies by the difference between TA and Ts.
<COOL>
TA (°C)
+3.0
HH
+2.5
(HH)
+2.0
H+ (HH)
+1.5
H (HH)
+1.0
L+ (H+)
+0.5
L (H)
Tsc
L (H)
–0.5
L (L+)
• Controlling operation in case when thermostat of remote
controller works is same as a case when thermostat of the
body works.
• Once the fan speed changes, it doesn't change for 3
minutes. However, you can change the fan speed using
the remote controller.
• When cooling operation has started, select a downward
slope for the fan speed, that is, the high position.
• If the temperature is just on the difference boundary, the
fan speed does not change.
• Mode in the parentheses indicates one in automatic
cooling operation.
<HEAT>
TA (°C)
(+0.5) +1.0
(0) Tsh
(-0.5) -1.0
(-1.0) -2.0
(-1.5) -3.0
(-2.0) -4.0
Value in the parentheses indicates one when thermostat of
the remote controller works.
Value without parentheses indicates one when thermostat of
the body works.
• Once the fan speed changes, it doesn't change for 3
minutes. However, you can change the fan speed using
the remote controller.
• When heating operation has started, select an upward
slope for the fan speed, that is, the high position.
• If the temperature is just on the difference boundary, the
fan speed does not change.
• Mode in the parentheses indicates one in automatic
heating operation.
• In TC ≥ 60°C, the fan speed increases by 1 step.
A
B
C
D
E
F
G
L (L+)
E
L+ (H)
H (H+)
D
H+
(HH)
C
HH
(HH)
B
A
– 29 –
Remarks
HH > H+ > H > L+ >
L > UL
TC: Indoor heat
exchanger sensor
temperature

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-hm401mut-eRav-hm561mut-eRav-hm561mut-tr

Table of Contents