Problem
Solution(s)
Switch On/
• After any Pulse or Interval entry, the Switch
Off Display
On or Switch Off LED does not alternate,
Doesn't
since most Pulse or Interval applications
Alternate
require only ON or OFF. Press OK without a
During
time entry to alternate the Switch On/Off
Programming
display if required.
Some
• All review should be done with only one circuit
Switching
enabled at a time. If more than one is enabled,
Times Don't
only events common to the circuits selected
Show During
will show during review. To see all possible
Review
scheduled events, the week long review should
be used. Events programmed via Day Group
or Copy Day methods will not show when
reviewing individual days or vice versa.
Difficulty in
• When using pulsed output for switching a
Programming/
latching relay or contactor without "self-
Reviewing On/
clearing" contacts, one circuit is dedicated to
Off Latching
the load Turn On Pulse and another to the
Pulse
Turn Off Pulse. The pulses are created by
or
turning the respective circuits On momentarily
Output to
(1 to 2 sec.). Therefore all events must be
Latching
programmed and will review as On Pulses.
Contactor
The On time(s) of the controlled load will be
Remains On
shown as On Pulses for one circuit and the Off
After an Off
time(s) will review as On Pulses for the other
Pulse
circuit. Note: Using the manual On/Off keys to
switch this type of contactor On or Off may not
provide the expected result and may cause damage
to the contactor coil. For this application external
Momentary Pushbutton may be added for both
circuits or the circuits may be programmed for
override pulses. Refer to the Programming
Examples booklet for more information.
36
NOTE: If you need more programming assistance, request form
#158ET9311, Programming Examples, which contains step-by-
step instructions for several complex programs.

ERROR MESSAGES

Pressing HELP when an error code is displayed will cause an error
message and recommended action to scroll on display. Press any
key to stop message and restore pre-error display.
ERR 01 Too many keys pressed or HELP key not pressed first
ERR 02 Numeric entry not applicable
ERR 03 AM - PM key entry not applicable
ERR 04 Clock time not setup
ERR 05 Clock date not setup
ERR 06 ASTRO not setup
ERR 07 HOLIDAY not setup
ERR 08 OVERRIDE not setup
ERR 09 ASTRO entry not applicable
ERR 10 COPY key not applicable
ERR 11 Unable to clear a set point in week long review mode –
set points may only be cleared from an individual
day's program
ERR 12 Internal calculation error – may not be recoverable –
reset the time switch
ERR 13 Day groups may not be copied to or from
ERR 14 No ON or OFF time entry is allowed when entering an
Astro Set Point
ERR 15 A day may not be copied to itself or to a day which has
already been programmed.
ERR 16 February 29th is only permitted in leap year
ERR 17 No circuit selected–select a circuit using the circuit
enable switches
ERR 18 Astro entry is out of limits–SUNRISE must be before
noon and SUNSET must be after noon. SUNSET must
not be within 5 hours of SUNRISE.