• Insert the rubber stopper securely, all the way to the base, in order to prevent water leakage.
• The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe.
(Vinyl tube; pipe size: 20 mm; outer dimension: 26 mm)
• Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets
from forming. (Refer to Fig. 21)
• Use the attached drain hose (1) and clamp (2).
Insert the drain hose into the drain socket, up to the gray tape.(Refer to Fig. 22)
Tighten the clamp until the screw head is less than 4 mm from the hose. (Refer to Fig. 23)
(Be careful of the installation direction. Install so that the clamp metal does not contact the intake grill.)
• Wrap the attached sealing pad (8) over the clamp and drain hose to insulate. (Refer to Fig. 23)
• No folding of drain hose inside the indoor unit. (Refer to Fig. 24)
(If there is slack in the drain hose, it may cause damage to the intake grill.)
(When drain hose is connected)
Good
Tilt down
Sealing
pad (8)
(attached)
Clamp metal (2)
(attached)
< Facing rear right or right >
(2) Confirm that smooth drainage is achieved after the piping work.
• Add 600 cc of water in the drain pan from the air outlet for confirming drainage. (Refer to Fig. 25)
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sew-
age might enter the indoor unit through the drain pipes and corrode the heat exchanger.
11
Wrong
Do not lift
Fig. 21
< Facing rear left or left >
Fig. 23
Pump used for
kerosene stoves.
Bucket
Fig. 25
Make sure there
is no slack
Taping area
(Gray)
Make sure it is
not in the water
Clamp metal (2)
(attached)
Sealing pad (8)
(attached)
(Length : mm)
Air outlet
Clamp metal (2) (attached)
Drain hose (1)
(attached)
Fig. 22
Wrong
Fig. 24
English

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-32tmjplCs-63tmjplCs-100tmjpl

Table of Contents