Field Setting - Panasonic Urban Multi Series Installation Manual

Hide thumbs Also See for Urban Multi Series:
Table of Contents

Advertisement

10. FIELD SETTING

Field setting must be made from the remote controller in accordance with the installation condition.
• Setting can be made by changing the "Mode No.", "FIRST CODE NO.", and "SECOND CODE NO.".
• For setting and operation, refer to the "FIELD SETTING" in the installation manual of the remote controller.
10-1 Setting ceiling height
• Select the SECOND CODE NO. that corresponds to the ceiling height. (Refer to Table 3).
(SECOND CODE NO. is factory set to "01" for a ceiling height of 2.7m or less.)
Table 3
Ceiling height (m)
2.7 or less
2.7- 3.5
10-2 Setting air filter sign
• Remote controllers are equipped with liquid crystal display air filer signs to display the time to clean air fil-
ters.
• Change the SECOND CODE NO. according to Table 4 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to "01" for filter contamination-light.)
Table 4
Setting
Air filter contamination-
light
Air filter contamination-
heavy
When using wireless remote controllers
• When using wireless remote controllers, wireless remote controller address setting is necessary. Refer to
the installation manual attached to the wireless remote controller for setting instructions.
10-3 Control by 2 Remote Controllers (Controlling 1 indoor unit by 2 remote controllers)
• When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB".
MAIN/SUB CHANGEOVER
(1) Insert a wedge-head screwdriver into the recess between
the upper and lower part of remote controller and, working
from the 2 positions, remove carefully the upper part. The
remote controller PC board is attached to the upper part of
remote controller.
(2) Turn the MAIN/SUB changeover switch on one of the two
remote controller PC boards to "S". (Leave the switch of the
other remote controller set to "M".)
English
Mode No.
13 (23)
Spacing time of display air filter
sign (long life type)
Approx. 2500 hrs
Approx. 1250 hrs
FIRST CODE NO.
0
FIRST CODE
Mode No.
10 (20)
Insert the screwdriver
here and gently work
off the upper part of
remote controller
(Factory setting)
(Only one remote
controller needs
to be changed if
factory settings
have remained
untouched.)
SECOND CODE NO.
01
02
SECOND
NO.
CODE NO.
01
0
02
Upper part of
remote controller
Lower part of
remote controller
S
S
M
Remote
controller
PC board
S
M
16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-32tmjplCs-63tmjplCs-100tmjpl

Table of Contents