Programming
NAC #
1=ENABLED

2=TYPE

3=SILENCEABLE

NAC Screen #1
88
3.6.5.5.2 Type
The main circuit board NAC type can be programmed by pressing 2 while viewing
NAC Screen #1. The following screen will be displayed. Press the down arrow key
to view additional screens:
1=BELL
2=HORN
3=STROBE
Select the NAC device type by pressing the number corresponding to the type in the
appropriate screen. When the selection is made, the display will return to NAC
Screen #1.
The following table contains NAC type codes and their functions:
NAC Type Code
Special Function
Bell
None
Horn
None
Strobe
None
Synced Strobe
Synchronized to manufacturer
Strobe Sil Sync
Same as Synced Strobe but Silence turns off audible & visual devices
Siren Circuit
None
3.6.5.5.3 Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to
Silenceable No. This will prevent the selected main circuit board NAC from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each
press of the 3 key will cause the display to toggle between Silenceable Yes and
Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual
devices is programmed for silenceable and the Synced Strobe feature is selected,
only the audible devices will be turned off if the Silence key is pressed or if the
Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to
operate. If the Strobe Sil Sync feature is selected, Silence or Autosilence will turn
off both audible and visual devices.