Correlations
Figure C.1 Municipal Box Connected to F Transmitter Module
Polarities shown in alarm condition
MS-9200UDLS PN 52750:A 11/04/05
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for
separate transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to
Municipal Box.
2. Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of
4XTMF module and circuit.
3. Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory
relay.
4. Refer to "4XTMF Transmitter Module Installation" on page 38 for detailed
information.
Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module
NFPA Standard-Specific Requirements
Municipal Box
Circuit
Gamewell Model M34-56
Local Energy Municipal Box
Nonpower-limited
-
+
F
FIRE
+
-
175