Use Of Furnace As Construction Heater; General - Lennox DAVE SIGNATURE SL280DFV Installation Instructions Manual

Gas furnace downflow air discharge
Hide thumbs Also See for DAVE SIGNATURE SL280DFV:
Table of Contents

Advertisement

GAS UNIT
Dampers
(open during heating
operation only)
FIGURE 1
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE - This furnace is designed for a minimum continu-
ous return air temperature of 60°F (16°C) or an intermittent
operation down to 55°F (13°C) dry bulb for cases where a
night setback thermostat is used. Return air temperature
must not exceed 85°F (29°C) dry bulb.
The SL280DFV furnace may be installed in alcoves, clos-
ets, attics, basements, garages, and utility rooms in the
downflow position.
This furnace design has not been CSA International certi-
fied for installation in mobile homes, recreational vehicles,
or outdoors.

Use of Furnace as Construction Heater

Lennox does not recommend the use of SL280DFV unitss
a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and op-
eration of the unit with clogged or misplaced filters will
damage the unit.
AIR HANDLER
Dampers
(open during cooling
operation only)
Page 5
SL280DFV units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
• The vent system must be permanently installed per
these installation instructions.
• A room thermostat must control the furnace. The use
of ixed jumpers that will provide continuous heating is
not allowed.
• The return air duct must be provided and sealed to the
furnace.
• Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
• Air filters must be installed in the system and must be
aintained during construction.
• Air filters must be replaced upon construction comple-
tion.
• The input rate and temperature rise must be set per the
furnace rating plate.
• One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc-
tion. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
• The furnace heat exchanger, components, duct sys-
tem, air filters and evaporator coils must be thoroughly
cleaned following final construction clean-up.
• All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified
according to these installation instructions.

General

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the
following general recommendations must be considered
when installing a SL280DFV furnace:
Place the furnace as close to the center of the air
distribution system as possible. The furnace should
also be located close to the chimney or vent termi-
nation point.
Do not install the furnace where drafts might blow
directly into it. This could cause improper combus-
tion and unsafe operation.
Do not block the furnace combustion air openings
with clothing, boxes, doors, etc. Air is needed for
proper combustion and safe unit operation.
When the furnace is installed in an attic or other
insulated space, keep insulation away from the fur-
nace.