Specifications - Omega Engineering HX92B Series User Manual

Relative humidity transmitters
Table of Contents

Advertisement

8

Specifications

Section 8 - Specifications
Measuring Range:
Accuracy Range:
Hysteresis:
Repeatability:
Resolution:
Response Time:
Sample Rate:
Operating Temperature:
Input Power
Max Loop Resistance:
Resistance:
Sensor Type:
Enclosure Housing:
Connections:
Dimensions:
Weight:
* 4 to 20 mA, 0 to 1 volt, 0 to 5 volts or 0 to 10 volts output. See page 2.2 for
model numbers.
8-1
4-20mA:
0-1V:
0-5V:
0-10V:
(4 to 20mA)
HX92B (*):
HX92B (*)-D:
HX92B (*)-RP1:
0 to 100%
±2.5% from 20 to 80% RH, ±3.5% from 5 to 20%
and 80 to 95% RH; ±4% from 0 to 5% and 95 to
100% RH
±1%
±0.1%
0.1%
8 Seconds typical
1 sample every 4 seconds.
-30 to 75°C
9 to 30 Vdc @ 50mV
9 to 30 Vdc @ 50mA
9 to 30 Vdc @ 50mA
12 to 30 Vdc @ 50mA
200 Ohms @ 9 Vdc supply voltage
1,300 Ohms @ 30 Vdc supply voltage
Ohms = ((V supply – 4 V) / .02 A)
Max. Load (min. resistance)
1.25K for outputs: 0 – 1 Vdc, 0 – 5 Vdc
2.40K for 0 – 10 Vdc output
Digital Sensor
Gray Polycarbonate, NEMA 13 (IP 54).
Nylon, Liquid-tight with neoprene gland for 2.29
to 6.73 m (0.09 to 0.265") diameter cable, internal 5
position terminal block accepts wire size from 14
to 22 gauge wire.
See "Mounting" Section
124 g (4.4 oz)
132 g (4.7 oz)
230 g (8.1 oz)