Superior WRT6050 Installation And Operation Instruction Manual page 13

Indoor wood burning fireplace
Table of Contents

Advertisement

Terminations/Spark Arrestor
The fireplace system must be terminated with the listed round top or
chase terminations. In any case, refer to the installation instructions
supplied with the termination.
CAUTION: Do not seal openings on the rooftop
flashing. Follow the installation instructions provided
with the termination being used.
Stainless Inner
Flue Pipe
Secure Termination
to Outer Pipe with 3
Screws
Overlap Shingles (Top and
Sides of Flashing Base)
Figure 18 - Termination
CHASE INSTALLATIONS
Instructions for chase installations are included with the chase style
termination chosen. In a multiple chase installation, be sure to provide
adequate distance between terminations to prevent smoke spillage
from one termination to another. We suggest that terminations be
separated at least 24", center to center and stacked at a vertical height
difference of 18" (see Figure 19).
Note: If a decorative shroud is to be installed, contact the manufac-
turer for specifications.
24" (610 mm)
24" (610 mm)
Figure 19 - Multiple Chase Installation
126595-01_E
VENTING INSTALLATION Continued
10 FOOT RULE
All flue gas outlet chimney terminations must extend a minimum of
3 feet in height above the highest point where it passes through the
roof and must be at least 2 feet above the highest point of the roof
that is within a horizontal distance of 10 feet (see Figure 20).
RLT-12D
Level of Flue
Gas Outlet
Waterproof
Caulking
Storm
Collar
Flashing
FINISHING FIREPLACE
Combustible materials, such as wallboard, sheet rock, drywall, plywood,
etc. may make direct contact with sides and top around the fireplace
Underlap Shingles
face. It is important that combustible materials do not overlap the face
itself. Brick, glass, tile or other noncombustible materials may overlap
the front face provided they do not obstruct essential openings like
louvered slots or any other opening. When overlapping with a noncom-
bustible facing material, use only noncombustible mortar or adhesive.
18" (458 mm)
Min. Typ.
Superiorfireplaces.US.com
10'
(3.05 m)
3'
2' (0.61 m) Min.
(0.91 m)
Min
Figure 20 - 10 Foot Rule
Level of Flue
Gas Outlet
10'
(3.05 m)
2' (0.61 m)
3'
Min.
(0.91 m)
Min
13