Hazardous Locations Installations; Hazardous Locations Certifications - Emerson Rosemount 3144P Reference Manual

Smart temperature transmitter
Hide thumbs Also See for Rosemount 3144P:
Table of Contents

Advertisement

Reference Manual
00809-0100-4021, Rev AA
March 2002
Appendix B
HAZARDOUS
LOCATIONS
INSTALLATIONS
HAZARDOUS
LOCATIONS
CERTIFICATIONS
www.rosemount.com
Hazardous Area Approvals
Hazardous Locations Installations . . . . . . . . . . . . . . . . . . page B-1
Hazardous Locations Certifications . . . . . . . . . . . . . . . . . page B-1
Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-5
The transmitter is designed with explosion-proof housings and circuitry
suitable for intrinsically safe and non-incendive operation. Each transmitter is
clearly marked with a tag indicating the approvals. To maintain certified
ratings for installed transmitters, install in accordance with all applicable
installation codes and approval drawings. Verify that the operating
atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications. Both transmitter covers must be fully engaged to meet
explosion proof requirements.
Factory Mutual (FM) Approvals
E5 Explosion Proof for Class I, Division 1, Groups A, B, C, and D (T
Dust ignition proof for Class II, Division 1, Groups E, F, and G, Class III,
Division 1, hazardous locations.
Non-Incendive for Class I, Division 2, Groups A, B, C, and D (T
Indoor and outdoor use. Explosion Proof approval only when connected
in accordance with Rosemount drawing 03144-0320. Ambient
temperature Limit –50 to 85 °C (-58 to 185 °F). For Group A, seal all
conduits within 18 inches of enclosure; otherwise, conduit seal not
required for compliance with NEC 501-5a(1).
K5 Combination of E5 and the following:
Intrinsically Safe for Class I, II, and III, Division 1, Groups A, B, C, D, E,
A). Ambient temperature Limit –60 ≤ T
F, and G (T
4
140 °F).
Non-Incendive Field Circuit for Class I, II, III; Division 2, Groups A, B, C,
D, F, and G. Intrinsically Safe and Non-Incendive field circuit approval
only when installed in accordance with Rosemount drawing 03144-0321.
Canadian Standards Association (CSA) Approvals
K6 Combination of the following:
Explosion Proof for Class I, Division 1, Groups A, B, C, and D; Class II,
Division 1, Groups E, F, and G; Class III, Division 1 hazardous locations.
Class I, Division 2, Groups A, B, C, and D. Factory sealed. Intrinsically
Safe for Class I, Division 1, Groups A, B, C, and D; Class II, Division 1,
Groups E, F, and G; Class III, Division 1 hazardous locations when
installed in accordance with Rosemount drawing 03144-0322.
Model 3144P
).
5
A).
4
≤ 60 °C (–76 ≤ T
a
a