KEY OPTION
■ AMSSSSSMSSS series
Tact S/W
# of Times
One time of
K1
long press
1time
2times
K1
3times
4times
5times
1time
2times
K2
3times
4times
5times
K3
■ RDSSSMSSSS series
Tact S/W
# of Times
1time
2times
K1
3times
4times
5times
1time
2times
K2
3times
4times
K3
■ K4 Display Order
K4
1time
Operating frequency of current compressor
Low pressure value (AMSSSSSMSSS series)
2times
Target frequency (RDSSSMSSSS series)
3times
Outdoor temperature
4times
Discharge temperature of compressor
5times
OLP temperature
6times
COND temperature
7times
Double-pipe heat exchanger temperature
8times
High pressure value
9times
Outdoor fan RPM
10times
ESC (EVI) EEV Operating Value
11times
MAIN EEV Operating Value
12times
Current Value
13times
Number of Indoor Unit Connections
14times
Number of Indoor Units Operating
15times
Total Capacity of Connected Indoor Units
Item
Auto Commissioning & Management System
Charge heating refrigerant
Test heating operation
Heating pump out
Vacuum
Finish
Charge cooling refrigerant
Test cooling operation
Cooling pump down
Test operation for checking refrigerant level
Finish
Reset
Item
SEG1
Charge heating refrigerant
Test operation of heating
Heating pump out
Vacuum
Finish
Charge cooling refrigerant
Test operation of cooling
Cooling pump down
Finish
Reset
Display Details
SEG1
SEG2
SEG3
SEG2
SEG3
Display Value (Ex.)
SEG1
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
56
SEG4
Note
SEG4
Note
Meaning
SEG 2,3,4
0,4,2
42Hz
1,7,5
1.75Mpa
0,6,4
64Hz
1,5,8
15.8℃
7,7,2
77.2℃
5,5,8
55.8℃
3,1,7
31.7℃
1,8,9
18.9℃
2,1,0
2.10MPa
6,0,0
600 RPM
0,8,0
80 STEP
1,0,0
1000 STEP
1,0,0
10A
0,0,7
7℃
0,0,4
4℃
1,4,5
14.5kcal/hr