Samsung AM030RXMDEH/EU Service Manual page 50

System air conditioner
Table of Contents

Advertisement

PCB Diagram
▒ MAIN PCB : AM040/050KXMDEHS, AM040/050KXMDCHS, AM030RXMDEHS
CN101-AC INPUT
#1~#3 : 220~240Vac
CN704-4WAY VALVE 2
#1~#3 : 220~240Vac
CN806-E2P MODULE
CN804-EEV 3
#1~4 : EEV signal
#5 : DC 12V
CN305-COMM INV PBA
CN401-MID P SENSOR
#1 : INPUT
#2 : GND
#4 : VCC
CN701-HOT GAS
#1~#3 : 220~240Vac
CN403- TEMP SENSOR
#1 : OUT TEMP
#2,4,6,8: GND
#3 : COND TEMP
#5 : DISCHARGE TEMP
#7 : OLP SENSOR
CN002-HIGH P S/W
#1 : INPUT
#2 : GND
CN406-
CN501- SELECT COOLING ONLY
CN302-COMM SUB PBA
CN702-4WAY VALVE 1
#1~#3 : 220~240Vac
CN306-MICOM DOWNLOAD
#1~#10 : Micom down
CN803-EEV 2
#1~4 : EEV signal
#5 : DC 12V
CN805-EEV 4
#1~4 : EEV signal
#5 : DC 12V
CN401-LOW P SENSOR
#2 : INPUT
#3 : GND
#4 : VCC
CN303-COM INDOOR UNIT
50
(cont.)
CN703-BASE HEATER
#1~#3 : 220~240Vac
CN802-EEV 1
#1~4 : EEV signal
#5,6 : DC 12V
CN001-Flow S/W
#1 : INPUT
#2 : GND
CN801- EXTERNAL CONTROL
OUT
#1,3 : DC 12V
#2 : ERROR CHECK OUT
#4 : COM CHK OUT
CN401-HIGH P SENSOR
#1 : INPUT
#3 : GND
#4 : VCC
CN103-EARTH