6. Mode Settings
■ Setting mode 1
<Operating procedure>
➀
Press and hold the
(VENTILATION) button simultaneously for 4
seconds or longer.
➁
Press the temperature setting
buttons to change the item code. The item codes
and setting data are shown in the table of "List of
Item Codes" on the next page.
➂
Press the timer time
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, "SET DATA" display stops blinking
and remains lit.)
➃
During this mode, "SET DATA" is displayed,
blinking. The outdoor unit address display section
displays "ALL," the item code and number (DN
3
value in the table), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The
display changes between the first 4 digits (Fig.
and the last 4 digits (Fig.
When the first 4 digits are displayed, the top dot of
the colon is illuminated.)
➄
To exit the setting mode, press the
button.
DN
Snowfall sensor usage
Outdoor unit fan Quiet
mode
Energy saving mode
Energy saving operation
plug
Demand 1 current
Demand 2 current
(CHECK) button and
and
and
buttons to
B
).
(CHECK)
Parameter
0 = Sensor input not present. Control is performed.
1 = Sensor input present. Control is performed.
2 = Sensor input not present. Control is not performed.
3 = Sensor input present. Control is not performed.
0 = Disabled
2 = Quiet mode 2
4 = Quiet mode 4
0 = None
1 = Discharge temp. control only (Mode 3)
2 = Demand only (Mode 2)
3 = Discharge temp. control + Demand (Mode 1)
0 = Independent
1 = All indoor units linked
0 = 0% 1 = 40 ... 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
0 = 0% 1 = 40 ... 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
Outdoor Unit Maintenance Remote Controller
A
Display of fi rst 4 digits
5
1
B
Display of last 4 digits
A
)
5
1
A
B
and
(Example shows display of 0000 0001.)
Description
1 = Quiet mode 1
3 = Quiet mode 3
3 - 12
W-2WAY ECO-i SYSTEM
3
3
are displayed alternately.
2
2