14. Current Protection

(1) Fan motor
Alarm
P22
Occurs when the fan motor detects overcurrent, or when the motor is locked and
does not turn.
(2) Inverter compressor
Alarm
P16
Occurs during ordinary operation when overcurrent (27.0A) is detected.
1
P26
Occurs under the same conditions as P16 when the inverter compressor is operating
at or above 80 Hz.
P29
Occurs when missing phase or overcurrent (48 A) is detected at inverter compressor
start. (the alarm at frequencies below 25Hz)
H31
Occurs when HIC detects overcurrent (75A), or when an abnormal high temperature
(150 ℃) is reached.
The inverter current includes a primary current and secondary current. The alarm judgment utilizes both cur-
rents. Generally, the secondary current is larger that the primary current.
(3) Constant-speed compressor
An alarm occurs when overcurrent or lock current is detected.
List of overcurrent and lock currents
Outdoor unit
type
705
905
1155
1305
1405
List of Alarms
Compressor
No.
Detected
current
Alarm display
(4) CT circuit detection trouble
Compressor 1 (inverter
compressor)
Compressor 2 (constant-
speed compressor)
Compressor 3 (constant-
speed compressor)
If the inverter compressor operating frequency is low, the current value is also low. Therefore this alarm is
detected only when the compressor is stopped.
The operating current of the constant-speed compressors is always higher than 1.5 A. Therefore, this alarm
occurs as the result of an open circuit or failure.
Description
Description
Constant-speed
Overload
compressor
current [A]
-
-
Compressor 2
11.6
Compressor 2
12.1
Compressor 2
11.6
Compressor 3
11.6
Compressor 2
12.1
Compressor 3
12.1
Compressor 2
Lock
Overcurrent
current
H11
H12
Alarm
H03
Occurs when an open CT circuit is detected in the inverter
compressor.
H13
Occurs when a current value of 1.5 A or less is detected
when the constant-speed compressor is operating.
H23
Occurs when a current value of 1.5 A or less is detected
when the constant-speed compressor is operating.
Lock current
[A]
-
13.7
14.3
13.7
13.7
14.3
14.3
Compressor 3
Lock
Overcurrent
current
H21
H22
Description