7 - TOUCH PILOT CONTROL: DETAILED MENU STRUCTURE

7.1 - Main menu

Icon
Displayed text*
General Parameters
Temperatures
Pressures
Inputs Status
Outputs Status
Pump Status
Run Times
Modes
Setpoint Table
Energy monitoring
Configuration Menu
Trendings
* Depends on the selected language (English by default).
** The Trendings menu is displayed in form of a graph. For more information about Trendings, see section 5.9.
CAUTION: Since specific units may not include additional features, some tables may contain parameters that cannot be
configured for a given unit.
General Parameters Menu – GENUNIT
No.
Name
1
CTRL_TYP
2
STATUS
3
CHIL_S_S
4
CHIL_OCC
5
min_left
6
HEATCOOL
7
HC_SEL
8
Status
Unit
0 to 2
-
-
-
disable/enable
-
no/yes
-
-
min
Cool
0 to 2
-
Description
General parameters
Temperatures
Pressures
Inputs status
Outputs status
Pump status
Run times
Modes
Setpoints
Energy monitoring
Configuration menu
(see section 7.2)
Trendings **
Displayed text*
Local=0 Net.=1 Remote=2
Run Status
Net.: Cmd Start/Stop
Net.: Cmd Occupied
Minutes Left for Start
Heat/Cool status
Heat/Cool Select
0=Cool. 1=Heat. 2=Auto
Associated table
GENUNIT
TEMP
PRESSURE
INPUTS
OUTPUTS
PUMPSTAT
RUNTIME
MODES
SETPOINT
ENERGY
CONFIG
TRENDING
Description
Operating mode:
0 = Local
1 = Network
2 = Remote
Off, Running, Stopping, Delay, Trip out, Ready,
Override, etc.
Unit start/stop via Network: When the unit is in
Network mode, start/stop command can be forced
Unit time schedule via Network: When the unit is in
Network mode, the forced value can be used instead
of the real occupancy state
Minutes before the unit start-up
Heating/cooling status: 30KAV are cooling-only
chillers ("heating" is NOT available)
Heating/cooling selection (only cooling mode is allowed)
0 = Cooling mode
1,2 = not applicable to this unit
17