Hmi Functions - Trane Arctic Manhattan Gen II Installation, Operation And Maintenance Manual

Air-cooled modular chiller
Table of Contents

Advertisement

HMI Functions

1 - HMI Software Version
Calls up the pop-up window
Project Name: HMI software project name; Software
Version.: HMI software version. Consists of 4 two-digit
numbers. First 2 numbers: major and minor software
revision. Third number stands for special software
revision. If any project has the special software, this
number would be different from '00'. Fourth number
stands for beta software revision.
2 - HMI User Management / Login
Current User: indicates which user is currently logged
in. There are three users for the HMI: 'user', 'tech' and
'admin'.
user - (default user) has access to viewing data
mostly. The only allowed controls for this user are:
turning chiller bank on / off and turning
compressors on / off (described below). There is no
password for this user;
tech - higher access than user but still limited.
Beyond 'user' 'tech' can adjust cooling / heating
setpoints, turn separate modules on / off and has
access to some machine basic temperature control
settings (described below). Password is 'tech2';
admin - full access to all the settings.
Log in: Calls up user logging screen where user name
and password have to be entered
Log Out: unhidden for 'admin' and 'tech' users only. It
logs out from 'admin' or 'tech' user to a default user,
which is 'user.'
ARTC-SVX001B-EN
Figure 13. User logging screen
3 - Module Layout Access
The module layout access button provides fast access
to the module layout screen.
4 - Active Alarm Access
The active alarm access button provides fast access to
a list of currently active system alarms.
5 - Setpoint
Calls up cooling / heating setpoint pop-up screens
respectively depending on the Mode. Accessible for
'tech' only. These boxes themselves display the
resulting cooling / heating setpoint used for machine
temperature control. Note: The only box on these pop-
ups accessible for 'tech' user. The other settings are
view-only. See
Figure 14, p. 27
Figure 14. Cooling / heating setpoint
6 - Controlled Temperature Reading
7 - System Temperature Sensors Reading
Based on chilled water entering / leaving temperatures
for Cooling Mode and hot water temperatures entering
/ leaving for Heating Mode
8 - System Status
Possible Options:
System ON. System is not off by any of the
conditions below.
Phase Alarm. System is off by Phase Alarm if
common Phase Monitor is used per chiller.
O O p p e e r r a a t t i i n n g g P P r r o o c c e e d d u u r r e e s s
27