Model SCSS-700 Installation Manual
1. Place the network repeater on one of the 5815XL standoff sets. Use the standoff extenders
provided for better access to the fiber optic cables if there is a clearance issue.
2. Use the 20" ribbon cable to connect the SCSS-700 to the repeater board. Run an insulated
wire from the screw terminal labeled G (TB2) on the repeater to an earth screw terminal
on the control panel.
3. Place Jumpers J2 and J3 in the CLOSED position when there is a twisted pair cable
connected to port 1 of terminal block TB1. Each repeater has the ability to monitor for
earth ground faults on the twisted pairs connected to port 1of its terminal block TB1. Earth
fault detection for any wiring at Port 2 of TB1 is done at the next/previous repeater due to
these wiring connections being connected to Port 1of TB1 at the next/previous repeater.
When no twisted pair wiring is made to Port 1 of TB1 jumpers J2 and J3 must be left
OPEN at the repeater. This would be the case when using fiber optic cable or when Port 2
of TB1 is only being used.
4. On fiber optic repeaters, jumpers J4 through J9 are normally left OPEN. See IFP-RPT
installation instruction (p/n 9001-0061) for determining when to use J4 through J9. Fiber
optic ports that are not used must have their dust caps placed on the port.
5-6
Figure 5-5 Panel to Networked repeater connection