Stanley SCSS-700 Installation & Operation Manual page 35

Analog/addressable fire system
Table of Contents

Advertisement

Table 3-1: Current Draw Worksheet for LiteSpeed SLC Devices
Device
MMF-301Mini Monitor
MMF-300 Monitor
BG-12LX Pull Station
MDF-300 Dual Monitor
MMF-300-10 Monitor-10
CMF-300 Control
CMF-300-6 Control-6
CRF-300 Relay
CRF-300-6 Relay-6
MMF-302 Zone
MMF-302-6 Zone-6
B200SR Sounder Base
B224RB Relay Base
RT151/151 KEY
RA100Z
I300 (Isolator Module)
B224BI Isolator Base
Accessories Modules
5815XL SLC Expander
SCSS-700ANN Remote Fire
Alarm Annunciator
5824 Serial/Parallel Module
5496 Intelligent Power Module
5895XL Power Module
5865-4 LED Annunciator
(with reset and silence switches)
53722
# of Devices
Current per Device
(159 max/loop
Standby/Alarm
& 636 max/
1
panel)
Standby/Alarm:
Standby/Alarm:
SLC
Aux Pwr
SLC
Aux Pwr
Standby/Alarm:
Standby/Alarm:
Aux Pwr
SLC
Aux Pwr
SLC
(159 max/loop
Aux Pwr
& 636 max/
panel)
SLC
Standby/Alarm:
Alarm:
Alarm:
(318 max/loop
Standby/Alarm:
& 636 max/
Standby/Alarm:
panel)
5
Standby/Alarm:
(63 max)
Standby:
5
(63 max)
Alarm:
(2 max.)
Standby/Alarm:
5
Standby/Alarm:
(63 max)
5
Standby/Alarm:
(63 max)
5
Standby:
(63 max)
Alarm:
Before You Begin Installing
Standby
Current
0.375mA
0.75 mA
3.5 mA
Standby/
0.375mA
Alarm:
0.375mA
Standby/
1.7mA
Alarm:
7mA
Standby/
2.25 mA
Alarm:
2.25 mA
Standby/
8 mA
Alarm:
20 mA
0.255 mA
1.45 mA
Standby/
12 mA
Alarm:
90 mA
Standby/
Alarm
0.27 mA
Standby
50 mA
Alarm:
270 mA
Standby/
Alarm
2 mA
Standby:
1 mA
Alarm:
15 mA
Alarm:
0.7 mA
0.5 mA
7.5 mA
10 mA
0.45 mA
0.5 mA
55 mA
25 mA
50 mA
45 mA
10 mA
10 mA
35 mA
145 mA
Alarm
Current
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
3-9