Networking
between the repeater of panel 4 and panel 3.
Panel 5 is at the end of a direct connect BUS so its DIP switches 8, 9 and 10 must be ON to
provide the direct connect BUS termination.
Panel 6 looks like it is at the end of a direct connect BUS, but because it is also using a
repeater its DIP switches 8, 9 and 10 must be OFF. In this example, panel 6 is actually in the
middle of a direct connect BUS between panel 5 and the repeater of panel 6. Jumper J1 of the
repeater is placed (CLOSED) and provides the termination. Jumpers J2 and J3 for the repeater
must be OPEN because no wires are connected to the twisted pair Port 1 of TB1.
53722
5-13