Hydronic Piping; System Water Piping Methods; Low Water Cutoff Device; Chilled Water System - Lochinvar FTXL 1000 Installation & Operation Manual

Hide thumbs Also See for FTXL 1000:
Table of Contents

Advertisement

6

Hydronic piping

System water piping methods

The FTXL is designed to function in a closed loop system
pressurized to not less than 12 psi (83 kPa) (Non-metallic
system piping must have an oxygen barrier to be considered
a closed loop). A temperature and pressure gauge is included
to monitor system pressure and outlet temperature and
should be located on the boiler outlet.
It is important to note that the boiler has a minimal amount
of pressure drop which must be accounted for when sizing
the circulators. Each boiler installation must have an air
elimination device, which will remove air from the system.
Install the boiler so the gas ignition system components
are protected from water (dripping, spraying, etc.) during
appliance operation or basic service of circulator replacement,
valves, and others.
Observe a minimum of 1/4 inch (6 mm) clearance around all
un-insulated hot water pipes when openings around the pipes
are not protected by non-combustible materials.

Low water cutoff device

This boiler comes equipped with a low water cutoff device.
On a boiler installed above radiation level, some states and
local codes require a low water cutoff device at the time of
installation.

Chilled water system

If the boiler supplies hot water to heating coils in air handler
units, flow control valves or other devices must be installed to
prevent gravity circulation of heater water in the coils during
the cooling cycle. A chilled water medium must be piped in
parallel with the heater.

Freeze protection fluids

Freeze protection fluids for new or existing systems must
use glycol that is specially formulated for this purpose. This
includes inhibitors, which prevent the glycol from attacking
the metallic system components. Make certain to check that
the system fluid is correct for the glycol concentration and
inhibitor level. The system should be tested at least once
a year and as recommended by the producer of the glycol
solution. Allowance should be made for the expansion of the
glycol solution in the system piping.
Use only inhibited propylene glycol
WARNING
solutions, which are specifically formulated
for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used
in hydronic systems.

General piping information

All boiler piping must contain an
IMPORTANT
oxygen barrier. This will help prevent
any excess oxygen from entering the
system.
31
Installation & Operation Manual
Basic steps are listed below along with illustrations on the
following pages (FIG.'s 6-5 through 6-10), which will guide you
through the installation of the FTXL (reference FIG.'s 6-3A and
6-3B).
1. Connect the system return marked "Inlet".
2. Connect the system supply marked "Outlet".
3. Install purge and balance valve or shutoff valve and drain
on system return to purge air out of each zone.
4. Install a backflow preventer on the cold feed make-up
water line.
5. Install a pressure reducing valve on the cold feed make-up
water line, (15 psi (103 kPa) nominal). Check temperature
and pressure gauge (shipped separately), which should read
a minimum pressure of 12 psi (83 kPa).
6. Install a circulator as shown on the piping diagrams in this
section. Make sure the circulator is properly sized for the
system and friction loss.
7. Install an expansion tank on the system supply. Consult the
tank manufacturer's instruction for specific information
relating to tank installation. Size the expansion tank for the
required system volume and capacity.
8. Install an air elimination device on the system supply.
9. Install a drain valve at the lowest point of the system.
Note: The boiler cannot be drained completely of water
without purging the unit with an air pressure of 15 psi
(103 kPa).
10. This appliance is supplied with a relief valve sized in
accordance with ASME Boiler and Pressure Vessel Code,
Section IV ("Heating Boilers"). Pipe the discharge of the
safety relief valve to prevent injury in the event of pressure
relief. Pipe the discharge to a drain. Provide piping that is
the same size as the safety relief valve outlet. Never block
the outlet of the safety relief valve.
The relief valve, tee and any other necessary
NOTICE
fittings are shipped in the install kit with the
boiler and are to be field installed (FIG.'s 6-1
and 6-2).
11. Install a field supplied strainer/filter to prevent damage
to the heat exchanger caused by debris entering from the
system piping. When installing in a pre-existing system, a
strainer/filter capable of removing debris left in the system
is recommended.
12. Install a field supplied magnetic separator in the heating
system return line as close as practical to the boiler per the
manufacturer's instructions.
A magnetic separator is recommended when
NOTICE
a unit is installed in a retrofit system, or a
system containing steel and/or cast iron pipe.
See the piping illustrations included in this section, FIG.'s 6-5
and 6-10 for suggested guidelines in piping the FTXL.
Please note that these illustrations are meant
NOTICE
to show system piping concept only, the
installer is responsible for all equipment and
detailing required by local codes.

Advertisement

Table of Contents
loading

Table of Contents