Swinger Shutdown; Hardware Default; Communicator Reset/Update - DSC LE4020 Installation Manual

Lte cellular alarm communicator
Hide thumbs Also See for LE4020:
Table of Contents

Advertisement

LE4020/LE4020CF Installation Manual
LE4020/LE4020CF Reporting Codes
Zone 1 Activation
Zone 1 Restoral
Zone 2 Activation
Zone 2 Restoral
Zone 3 Activation
Zone 3 Restoral
Zone 4 Activation
Zone 4 Restoral
PSTN Line Down
PSTN Line Restoral
Periodic Test
Periodic Test with Trouble
Radio Activation
Internal Buffer Full
FTC Restoral
Firmware Update Successful
Firmware Update Fail
Firmware Update Begin
System Tamper
System Tamper Restore

5.7 Swinger Shutdown

To prevent "runaway" signals to the central station, the LE4020/LE4020CF is equipped with Swinger Shut-
down which limits certain trouble events to a maximum of four reports every 24 hours. The condition restores
and the counter resets at midnight. Swinger Shutdown applies to the following trouble conditions:
System Tamper/Restore
l
Low Battery Trouble/Restore
l
TLM Trouble/Restore
l
Input Power Trouble/Restore
l
FTC Restore
l
Zone inputs
l

5.8 Hardware Default

A hardware default updates the unit with the latest configuration from C24 Communications if:
The device was originally programmed incorrectly.
l
The unit was installed at a different location and then relocated to a new site.
l
A SIM card is being swapped.
l
To perform a hardware default, follow these steps:
1. Power down the unit (remove primary DC power and remove the backup battery) and remove all con-
nections to Zone1, Zone 2, PGM1 and PGM.
2. Connect a wire between Z2 (terminal 14) and PGM2 (terminal 8)or Z1 (terminal 13) and PGM1 (ter-
minal 7).
3. Power up the radio by connecting the battery (if present) first and then primary DC power.
4. Wait for 20 seconds and then completely power down the unit.
5. Disconnect the wire between the Zone and PGM terminals.
Note: Failure to perform hardware default will result in the unit transmitting with the previously programmed
configuration.

5.9 Communicator Reset/Update

Note: For UL864 Installations, installer will need to be on site.
The firmware of the device can be updated over Cellular or PC-Link:
When the firmware update begins, all LED are ON.
l
CID
SIA
Programmable
E301 991
AT 991
YES
R301 991
AR 991
YES
E200 992
FS 992
YES
R200 992
FV 992
YES
E110 993
FA 993
YES
R110 993
FH 993
YES
E300 994
YX 994 YES
R300 994
YZ 994
YES
E351 000
LT 000
FIXED
R351 000
LR 000
FIXED
E603 XXX RP XXX FIXED
E608 XXX RY XXX FIXED
R552 000
RS 000
FIXED
E624 000
JL 000
FIXED
R354 000
YK 000 FIXED
R901 000
LS 000
FIXED
E902 000
LU 000
FIXED
E901 000
LB 000
FIXED
E145 000
ES 000
FIXED
R145 000
EJ 000
FIXED
18
Comments
AC Loss*
AC Loss Restore *
Fire Supervisory*
Fire Supervisory Restore*
Fire *
Fire Restore *
System Trouble *
System Trouble Restore *
Telco 1 Fault
Telco 1 Fault Restore
Test Transmission <Receiver Path>
Test Transmission <Receiver Path>
Remote Programming Successful
Communications Restored
Expansion Module Tamper
Expansion Module Tamper Restore