Outputs; Activating The Outputs; Reporting Codes; Swinger Shutdown - DSC 3G4010 Installation Manual

3g hspa cellular alarm communicator
Hide thumbs Also See for 3G4010:
Table of Contents

Advertisement

Outputs

The 3G4010 has four programmable outputs to activate in response to the associated events. Refer to the 3G4010 Wiring Dia-
gram (Figure 2) at the back of this manual.

Activating the Outputs

The 3G4010 has four open collector outputs capable of a maximum of 50mA. Internal events on the 3G4010 can trigger the
outputs to turn on an LED or activate an input on the host panel. The default settings are as follows.
OUTPUT 1 Landline Trouble - Output is normally high and will switch to ground when the telephone line is down.
OUTPUT 2 Cellular Module or Network Trouble - Output is normally high and will switch to ground when the 3G4010 can not
communicate with the 3G or 2G network.
OUTPUT 3 Power Supply or Battery Trouble - Output is normally high and will switch to ground when there is a problem with
the power source.
OUTPUT 4 General Module Trouble - Output is normally low and will switch to high when a Cellular Network Trouble, Power
Supply/Battery Trouble, and/or a Failure to Communicate (FTC) trouble is detected.
NOTE: PGM4 must be connected to the control panel as shown in Figure 4 (Residential applications) or Figures 8- 9 (Com-
mercial applications). Program the control panel input Zone/Point as 24hr 'Supervisory' with keypad- only notification when
activated. Output 4 on the 3G4010 must be set as 'Active High'.
NOTE: Once an output has been activated automatically, it will not restore its state until all the causes of activation are cleared.

Reporting Codes

3G4010 Reporting Codes
Zone 1 Activation
Zone 1 Restoral
Zone 2 Activation
Zone 2 Restoral
Zone 3 Activation
Zone 3 Restoral
Zone 4 Activation
Zone 4 Restoral
PSTN Line Down
PSTN Line Restoral
Input Loss
Input Restoral
Low Battery Alert
Low Battery Restoral
Periodic Test
Periodic Test with Trouble
Radio Activation
Internal Buffer Full
FTC Restoral
Firmware Update Successful R901 000 LS 000
Firmware Update Fail
Firmware Update Begin
System Tamper
System Tamper Restore
* C24 Communications default value

Swinger Shutdown

To prevent "runaway" signals to the central station, the 3G4010 is equipped with Swinger Shutdown which limits certain trouble
events to a maximum of four reports every 24 hours. The condition will restore and the counter will reset at midnight. Swinger
Shutdown applies to the following trouble conditions:
System Tamper/Restore
l
Low Battery Trouble/Restore
l
TLM Trouble/Restore
l
CID
SIA
Programmable
E11A 991 FA 991
R11A 991 FH 991
E12A 992 PA 992
R12A 992 PH 992
E13A 993 BA 993
R13A 993 BH 993
E3AA 994 YX 994
R3AA 994 YZ 994
E351 000 LT 000
FIXED
R351 000 LR 000
FIXED
E337 000 YP 000
FIXED
R337 000 YQ 000
FIXED
E338 000 YT 000
FIXED
R338 000 YR 000
FIXED
E603 XXX RP XXX
FIXED
E608 XXX RY XXX
FIXED
R552 000 RS 000
FIXED
E624 000 JL 000
FIXED
R354 000 YK 000
FIXED
FIXED
E902 000 LU 000
FIXED
E901 000 LB 000
FIXED
E145 000 ES 000
FIXED
R145 000 EJ 000
FIXED
12
Comments
YES
Delayed 24 Hour Fire *
YES
Delayed 24 Hour Fire Restore *
YES
Panic Alarm *
YES
Panic Alarm Restore*
YES
Burglary *
YES
Burglary Restore *
YES
System Trouble *
YES
System Trouble Restore *
Telco 1 Fault
Telco 1 Fault Restore
Power Supply Trouble
Power Supply Trouble Restore
Transmitter Battery Trouble
Transmitter Battery Restore
Test Transmission <Receiver Path>
Test Transmission <Receiver Path>
Remote Programming Successful
Communications Restored
Expansion Module Tamper
Expansion Module Tamper Restore