Convertible air handlers

Advertisement

Installer's Guide
SCREWS 5-8
LOCATED ON
LEFT SIDE
3
CLOSEUP OF SPEAR LOCATIONS
2 PIECE WRAPPER SPEAR
4
b. Remove the factory installed baffle assembly
from the apex of the coil by using a 5/16" nut-
driver to remove the screws.
baffle with the factory supplied narrow coil
baffle using the screws removed previously (See
Figure 5). Reinstall coil assembly.
4
When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.
c. Position unit on Pedestal or other suitable foun-
2
4
1
3
5
d. If a return air duct is connected to the air han-
e. On units with sheetmetal returns: Return ple-
f. No sheetmetal screws may be used to attach re-
g. Pedestal and unit should be isolated from the
h. Openings where field wiring enters the
i. After ductwork connections are made, seal air-
DOWNFLOW
a. For maximum efficiency, the horizontal drip
Replace this
CAUTION
L
!
dation. If Pedestal is not used, a frame strong
enough to support the total weight must be pro-
vided. Provide a minimum height of 14 inches
for proper unrestricted airflow.
FOR MAXIMUM EFFICIENCY ON
HORIZONTAL LEFT,
UPFLOW AND DOWNFLOW
Remove
and
Discard
dler, it must be the same dimensions as shown
in the outline drawing.
num should be flanged. Sheetmetal screws must
be 1/2" in length or shorter.
turn duct work on the side of the unit.
foundation using a suitable isolating material.
cabinet must be completely sealed. Location
of power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electri-
cal knockouts. See Figure 11.
tight and per local codes.
tray should be removed. See Figures 6, 7 and 8.
Tray removal requires that the coil be removed
by sliding the coil out on the coil channel sup-
ports. The tray is detached by removing the
two screws at the drain pan and the two screws
holding the two brackets at the top of the coil.
Remove drip tray by gently breaking the seal
between the drip tray and drain pan.